Check that there is a neutral in the place where three-phase static generator connections are made
with neutral, SVGm-4WF-xxxx.
3.6.- DEVICE TERMINALS
The connections on the SVGm IP54 are located at the bottom of the cabinet. The lower windows on the
cabinet have to be used to route the cables into the device,
If dust can enter the device from the bottom, these windows will have to be machined and suitable
cable glands installed for the cables.
To access the connections for the current input and mains, the screws of the lower front cover have to
be loosened,
88
Ensure that the installation of the device in your electric distribution system (TN, VT, IT)
complies with current standards.
Do not install various static generators in series one after another in the same instal-
lation, configured to correct the same disturbances. This can produce an overcompen-
sation of the disturbances, which could cause instability in the mains (
Figure 4: Do not install various static generators in series.
Figure 5: Sliding windows for the connection wiring.
You should never remove the cover closest to the front part.
.
Figure 6
.
Figure 5
SVGm IP54
)
Figure 4