SVGm IP54
7.5.- cos Φ
Note: This screen is not visible on the "slave" devices.
The device has two reactive power compensation modes (
Figure 50).
Figure 50: Configuration screen: cos Φ (Mode 1 and Mode 2).
● Mode 1
In this mode, cos Φ is set to a fixed value. The device will attempt to ensure that the reactive power on
the mains side corresponds to the specified cos Φ.
Range of values: 0.7... -0.7
● Mode 2
In this mode, two limits are defined to form an acceptance range. The device will adjust the reactive
power on the mains side to keep cos Φ within the specified acceptance range.
This mode minimises the amount of power used by the device to compensate for reactive power, thus
reducing its energy consumption.
Range of values: 0.7... -0.7
Press the
key to save the modified settings.