7.8.- ETHERNET COMMUNICATIONS

The Ethernet communication parameters are configured in this screen,
By activating the DHCP option ☑ DHCP, the device assigns the IP automatically.
If this option is not activated, the parameters must be configured manually:
● IP Address, IP address.
● Netmask, subnet mask.
● Gateway, gateway.
Press the

7.9.- RS-485 COMMUNICATIONS

The RS-485 communications configuration in SVGm IP54 models is set to a Baud rate of 9600 bps, 8
data bits, 1 stop bit and no parity. Only the device's Modbus address can be configured,
● Modbus device, modbus address.
Press the
126
Figure 53: Configuration screen: Ethernet communications.
key to save the modified settings.
Figure 54: Configuration screen: RS-485 communications.
key to save the modified settings.
SVGm IP54
:
Figure 53
Figure 54
Instruction Manual
.