8.2.2.4.- SVGm IP54 Static var generator messages
Table 19: Modbus memory map: Static var generator messages (Table 1).
Parameter
Device status
For a system with devices in parallel, the parameter value is that of the device connected with RS-485.
(5)
Table 20: Modbus memory map: Static var generator messages (Table 2).
Parameter
Alarm messages
Table 21: Modbus memory map: Static var generator messages (Table 3).
Parameter
Initial Conditions for which the device does not start up.
For a system with devices in parallel, the parameter value is that of the device connected with RS-485.
(6)
Instruction Manual
(5)
Bit
0x0001
0x0002
0x0004
Bit
0x00000000
0x00000002
0x00000004
0x00000008
0x00000010
0x00000020
0x00000040
0x00004000
0x00008000
0x00010000
0x00100000
0x00200000
Bit
0x0001
0x0002
0x0004
0x0008
0x0010
0x0020
0x0040
0x0080
0x0100
0x0200
0x0400
Address
110
Description
Stop
1: ON
Start
0: OFF
Reset alarms
Address
105 (Hi value), 106 (Low value)
Description
There are no alarms
L1 overcurrent alarm
L2 overcurrent alarm
L3 overcurrent alarm
L1 overvoltage alarm
L2 overvoltage alarm
L3 overvoltage alarm
Temperature IGBT 1 alarm
Temperature Inductor 1 alarm
Initial Conditions Error
Contactor faults
Temperature Inductor 2 alarm
(6)
Discharging DC bus
Minimum Mains Voltage
Minimum temperature value
Frequency error
Charging DC bus
Minimum DC bus voltage
DC Bus imbalance
The device does not communicate
Minimum load current
Maximum charge current
Status
Address
108
Description
Polarity Error
131