7.4.- OPERATING LIMITS

Note: This screen is not visible on the "slave" devices.
In this screen,
● Min current
The minimum load current to start the static generator is configured with this parameter. Minimum
current feature is used to increase the system efficiency, by stopping the static generator when re-
quired. The SVGm IP54 will stop when the load current is below the entered value and will start when
it is higher.
Range of values:
Minimum value: 0 A
Maximum value: 5000 A
● Current limit
This parameter allows the maximum power of the static generator to be limited. The value is config-
ured as a percentage with respect to the device's rated power.
Range of values:
Minimum value: 20%
Maximum value: 100%
Press the
122
, the operating limits of the device are configured:
Figure 49
Figure 49: Configuration screen: Operating limits.
key to save the modified settings.