16 - LIMIT SWITCH
For proper operation of the unit, it is necessary to connect two
limit switches with a normally closed contact, that defines the
travel of the door during opening and closing.
Connect the opening limit switch (FCA) between terminals
H2 and H5.
Connect the closing limit switch (FCC) between terminals
H1 and H5.
H1H2 H3 H4 H5 H6 H7 H8 E1 E2 E3 E4 E5
FCA
FCC
The position of the limit switches is stored during the learning
procedure of the travel and during normal operation of the door
the unit expects to detect the limit switches in specific positions.
m
If in some cases the door does not reach the position
needed to activate the limit switch, you can set an additional time
by configuring the parameter
activated the door continues its movement up to the end of the
set time.
: if the limit switches is not
T.ADD
17 - INTERMEDIATE POSITIONS
Some functions of the unit are activated at some intermediate
positions of the door.
The intermediate positions can be detected in two ways:
• Additional switches connected to terminals H3 and H4
• Programming of some parameters that are based on a
percentage of the total travel
17.1 - SWITCHES
The activation of additional switches can control the following
operations:
1. Start of slowdown
• During the opening phase the slowdown starts when the
contact between the terminals H4 and H5 opens (configure the
parameter
on
ENCO
• During the closing phase the slowdown starts when the
contact between the terminals H3 and H5 opens (configure the
parameter
on
ENCO
NOTE: The parameter
FC.RA
time limit within which the limit switch must activate after the
slowdown is started. When the time set is run the door stops.
If set to
, the travel continues until reaching the limit switch.
NO
2. Partial opening position
The partial opening procedure ends when the contact between
the terminals H4 and H5 opens (configure the parameter
on
).
ENCO
INTRM
H1H2 H3 H4 H5 H6 H7 H8 E1 E2 E3 E4 E5
3. Masked operation of the photocell
The photocell, if activated by setting the
parameter on
MASK
terminals H3 and H5 is open (configure the parameter
on
or
INTRM
FC.RA
H1H2 H3 H4 H5 H6 H7 H8 E1 E2 E3 E4 E5
parameter
ENCO
- 38 -
).
FC.RA
).
FC.RA
involves setting a maximum
or
FOT1
, is blocked when the contact between
or
)
EN.1C
a
DEFAULT =
(no function)
NO
FOT2
ENCO