NOTE: Keep in mind that the altitude of the
installation place and the water temperature may
reduce the suction possibilities of the pump.
Altitude
Loss of head
0 m
500 m
1000 m
1000 mCL
NOTE: Beyond 80° C, plan to install the pump in
load.

5.2 Hydraulic connections

CAUTION! Danger of material damage!
The installation has to bear the pressure reached
when the pump runs at maximum frequency and
zero flow rate.
Ports
Suction
1"(26-34) 1"1/4(33-42) 1"1/2(40-49)
Delivery
1"(26-34)
- Connection by flexible hose with reinforcement
or rigid propeller.
CAUTION! Danger of material damage!
Connections has to correctly sealed: No air entrance
is allowed on the suction pipe which is showing a
mounting declivity 2 % (fig. 1).
- With rigid pipe, avoid the pump to bear the
weight of the pipes, use supports (fig. 1).
- The diameter of the pipe must never be smaller
than the suction/delivery ports.
- Limit the length of the suction pipe and avoid all
features that cause losses of head (bends, valves,
tapers).
CAUTION! Danger of material damage!
When the pump is under pressure, it is recom-
mended to connect the non-return valve to the
pump discharge to protect it against hammer blow
effects.

5.3 Electric connections

WARNING! Electrical connections shall only be
made by approved specialised electricians and in
compliance with the applicable regulations.
The electric characteristics (frequency, voltage,
nominal current) of the motor-converter are men-
tioned on the pump identification sticker (item 19).
Check that the motor-converter complies with the
mains supply used.
30
Temperature
Loss of head
0 mCL
20 °C
500 mCL
30 °C
40 °C
50 °C
60 °C
70 °C
80 °C
90 °C
100 °C
110 °C
120 °C
Tapped ports
200
400
800
1"(26-34)
1"1/4(33-42) 1"1/2(40-49)
• The electric protection of the motor is integrat-
ed into the converter. The parameters take into
account the characteristics of the pump and must
ensure its protection and the one of the motor.
• In case of impedance between earth and neutral
point, install a protection before motor-converter.
0.20 mCL
• Provide a fuse-disconnecting switch (type gF) to
0.40 mCL
protect the mains installation (fig. 1, 2, item 11).
0.70 mCL
NOTE: If you have to install a differential cir-
1.20 mCL
cuit-breaker for users protection, it must have
1.90 mCL
a delay effect. Adjust it according to the current
mentioned on the variator label.
3.10 mCL
Use power cables conforming with standards.
4.70 mCL
DANGER! Danger of death!
7.10 mCL
Do not forget to connect to earth.
10.30 mCL
The electric connection of the variator (fig. 3),
14.70 mCL
according to its operating modes (see chapter 6
20.50 mCL
for starting) has to comply with the schemes of
the following table.
CAUTION! A connection error would damage the
variator.
CAUTION! The power cable must never touch the
pipe or the pump; make sure that it is sheltered
from any humidity.
• You can change the orientation of the
motor-variator by quarter turn when removing
the fixing screws of the motor and reorientating
1600
the motor to the wished position.
2"(50-60)
• Place the screws back.
SALMSON 08/2016