6. Operation
6.1 Setting
6.1.1 Control elements
The converter operates using the following con-
trol elements:
Setting with encoder
• The selection of a new parameter is done only
with a simple rotation, « + » on right and « - »
on left.
• A short impulse on the encoder validates this
new setting.
Switch
ON
1
2
• This converter has got a block with two switches
with two positions each (fig. 3, item S):
• Switch 1 allows to change the « OPERATION »
mode [switch 1->OFF] to « SERVICE » mode
[switch 1->ON] and conversely.
The « OPERATION » position allows the selected
mode to run and hinders the access to parame-
ters input (normal operating). The « SERVICE »
position is used to enter the parameters of the
different operations.
• Switch 2 is for activating or deactivating the
« Access lock ».
1
2
4
6.1.2 Display structure
• As soon as the power supply of the converter
has been activated, a 2 second display test is
carried out, where all characters on the display
are shown.
Pos.
1
2
3
4
5
36
4
5
3
4
Description
Menu number
Value display
Units display
Standard symbols
Icon display
6.1.3 Description of standard symbols
Symbol
Operating in « Speed control »
mode.
Operating in « Constant pressure »
2
or « P.I.D. control » mode.
Input IN2 activated
(external setpoint).
Access locked.
When this symbol appears, current
settings or measurements cannot
be changed. Information displayed
is only in reading.
BMS (building management system)
PLR or LON is active.
Pump runs.
Pump stops.
6.1.4 Display
Display status page
• The status page is shown as the standard view
on the display.
The currently set setpoint is displayed.
Basic settings are displayed using symbols.
Example of display status page
NOTE: If the encoder is not activated within 30
seconds in all menus, the display returns to the
status page and the change is not registered.
Description
SALMSON 08/2016