Configuring Pv Power Plant Management - SMA FUEL SAVE CONTROLLER 2.0 Instrucciones De Uso

Ocultar thumbs Ver también para FUEL SAVE CONTROLLER 2.0:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

8 System Control
Procedure:
1. Go to Control Functions > FSC control functions > Genset setpoints via the page and menu selection.
2. Set the desired parameters (see Section 4.8.3, page 20).
8.4.3

Configuring PV Power Plant Management

Parameter overview
Figure 44: Inverter management: Management of the PV power plant: Switching inverters on and off
Parameter
Description
Enable
Enable this function
GenPwrAtNomIn-
Proportion of allowed nominal in-
vProp
verter power in relation to the to-
tal nominal power of all con-
nected Gensets
PvConTmOutTm
The FSC waits for this time in sec-
onds for the PV inverters to con-
nect. Otherwise it will throw a
timeout.
94
FSC20-BA-xx-20
Value
Explanation
Yes
Activates the function Yes
No
Deactivates the func-
tion
0% to 1000%
10 s to 86400 s
SMA Solar Technology AG
Default
value
100 %
600 s
User Manual

Capítulos

Tabla de contenido
loading

Tabla de contenido