Parameter
Description
IntGain
Integral gain for the PI controller,
a tuning parameter
TrackGain
An anti windup parameter.
Keep it around 50% of integral
gain
BackcalcGain
An anti windup parameter.
Keep it around 50% of integral
gain
EnableFeedForward
Enables the feed forward algo-
rithm
FeedForwardOffset
A tuning parameter for the feed
forward algorithm
FeedForwardGain
A tuning parameter for the feed
forward algorithm
* When the function Reactive Power Control is activated, the function Reactive Power Management must be deactivated (see
Section 8.2.2, page 80).
78
FSC20-BA-xx-20
Value
Explanation
0 to 10
0 to 10
0 to 10
Yes
Activates the feed for-
ward
No
Deactivates the feed for-
ward
-100000 kVAr to
+100000 kVAr
0 to 10
SMA Solar Technology AG
Default
value
0.1
0.05
0.05
Yes
0 kVAr
1