8 System Control
Parameter
Description
HysPc
Hysteresis of SOC range:
• If the battery state of charge
• If the battery state of charge
SocLimHiPc
Upper limit of SOC range
SocLimLoPc
Lower limit of SOC range
ToRdyTm
Time until module starts working
after battery power is not used:
• If the battery state of charge
• If the battery state of charge
PwrAtLimPc
Percentage of maximum avail-
able charge/discharge power to
limit the calculated setpoint
Requirement:
☐ You must be logged in as Installer.
Procedure:
1. Go to Control Functions > Battery control functions > SOC control via the page and menu selection.
2. Set the desired parameters (see Section 4.8.3, page 20).
86
FSC20-BA-xx-20
falls below the value of the
parameter SocLimLoPc, the
Fuel Save Controller begins
to charge the battery.
exceeds the sum of the
parameters SocLimLoPc
and HysPc, the Fuel Save
Controller stops charging the
battery.
upper limit is exceeded and
the delay time has elapsed,
the Fuel Save Controller
requests that the battery be
discharged.
falls below the lower limit
and the delay time has
elapsed, the Fuel Save
Controller requests that the
battery be charged.
Value
Explanation
0% to 100%
0% to 100%
0% to 100%
0 s to 36000 s
0% to 100%
SMA Solar Technology AG
Default
value
5 s
80 %
60 %
180 s
10 %