SMA Solar Technology AG
Requirement:
☐ You must be logged in as Installer.
Procedure:
1. Go to Control Functions > PV control functions > Reactive power management via the page and menu
selection.
2. Set the desired parameters (see Section 4.8.3, page 20).
8.2.3
Configuring MPP Calculation for PV Power Plant
Parameter overview
Figure 38: MPP Calculation: Specifications on the MPP calculation for the PV inverters
Parameter
Description
MppCalcGain
In case of an inaccurate calculation of the
maximum power point, it can be improved by
adjusting this factor.
MppCalcOffset
In case of an inaccurate calculation of the
maximum power point, it can be improved by
adjusting this offset.
MppNormOpCell-
Normal operating cell temperature of the PV
Temp
modules. Use the PV module datasheet as a
reference.
User Manual
Value
Default value
-1000 to +1000
1
-100000 to
0
+100000
-100°C to +100°C
25°C
FSC20-BA-xx-20
8 System Control
83