Configuring Gensets - SMA FUEL SAVE CONTROLLER 2.0 Instrucciones De Uso

Ocultar thumbs Ver también para FUEL SAVE CONTROLLER 2.0:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

SMA Solar Technology AG
Parameter
Description
Enable this gen-
Determines whether the
erator
Fuel Save Controller should take
the genset into account for con-
trol of the PV diesel hybrid system
Nominal active
Nominal power of the genset
power
IP address
IP address of the genset con-
troller (not applicable with a
higher-level control system)
Unit-ID (Mod-
Genset controller ID for the Mod-
bus/TCP)
bus/TCP protocol
Enable setpoint
Activates the dynamic specifica-
mechanism
tion of a setpoint for the reserve
power
7.2.5

Configuring Gensets

The system settings of the Fuel Save Controller can only be adjusted when the Fuel Save Controller is in STANDBY or
ERROR mode. The operating state STANDBY can be reached by stopping the SMA Fuel Save Controller.
The system settings for the gensets are located in the menus Genset general configuration and
Generator configuration Wizard: detailed configuration. The displayed parameters depend on which gensets
are used:
• Gensets without genset controllers (see Section 7.2.1, page 44)
• Parameters for gensets with genset controller easYgen-3000, connected via the CAN network (see
Section 7.2.2, page 45)
• Parameters for gensets with genset controller easYgen-3000, connected via the ESENET gateway (see
Section 7.2.3, page 47)
• Gensets with genset controller ComAp IG-/IS-NTC (see Section 7.2.4, page 48)
Requirement:
☐ You must be logged in as Installer.
User Manual
Value
Explanation
Yes
The Fuel Save Controller
takes the genset into ac-
count.
No
The Fuel Save Controller
does not take the genset
into account.
0 kW to 10000 kW
172.16.1.31 to
Address range defined by
172.16.1.38
the Fuel Save Controller for
gensets
1 to 254
Yes
Dynamic specification of
setpoints for the reserve
power is activated.
No
Dynamic specification of
setpoints for the reserve
power is deactivated.
7 System Settings
Default
value
No
0 kW
172.16.1
.31
0
No
FSC20-BA-xx-20
49

Capítulos

Tabla de contenido
loading

Tabla de contenido