7 System Settings
7 System Settings
7.1

Configuring the Utility Grid

The system settings of the Fuel Save Controller can only be adjusted when the Fuel Save Controller is in STANDBY or
ERROR mode. The operating state STANDBY can be reached by stopping the SMA Fuel Save Controller.
Requirement:
☐ You must be logged in as Installer.
Procedure:
1. Choose the menu Configuration Wizard via the page and menu selection.
2. In the Grid bar, select the [Adjust] button.
3. To activate the utility grid connection, set the parameter Enable to Yes.
4. To deactivate the utility grid connection, set the parameter Enable to No.
5. Select the [Apply] button. This will adopt the setting.
6. Select the [Continue wizard] button.
7. End the system settings (see Section 7.9.1, page 67).
7.2

Settings for the gensets

7.2.1

Parameters for Gensets without the Genset Controller

Genset general configuration
Parameter
Description
Remaining
Remaining number of config-
available de-
urable gensets
vices
Number of de-
Number of installed gensets
vices
Genset inter-
Type of genset interface
face Type
Generator configuration wizard: detailed configuration
Parameter
Description
Alias
Genset ID
44
FSC20-BA-xx-20
Value
Explanation
0 to 8
None
The genset is monitored via
the current and voltage
measurement of the
Fuel Save Controller. A
genset controller is not
used.
Value
Explanation
SMA Solar Technology AG
Default
value
0
None
Default
value
User Manual