System Control; Genset Control; Configuring The Minimum Genset Load Threshold - SMA FUEL SAVE CONTROLLER 2.0 Instrucciones De Uso

Ocultar thumbs Ver también para FUEL SAVE CONTROLLER 2.0:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

8 System Control
8 System Control
8.1

Genset control

8.1.1

Configuring the Minimum Genset Load Threshold

Parameter overview
Figure 30: Minimum Genset Load: Settings regarding the minimum load of the genset
Parameter
Description
DbTolPc
Deadband for error output re-
lated to the minimum genset load-
ing threshold in %.
DbTolTm
Deadband timer for error output
in seconds
GenPwrAtMinPc
Minimum genset loading of the
genset system in % of the nominal
genset active power
70
FSC20-BA-xx-20
Value
Explanation
-100% to 100%
0.1 s to 3600 s
0% to 100%
SMA Solar Technology AG
Default
value
10 %
60 s
30 %
User Manual

Capítulos

Tabla de contenido
loading