7 System Settings
Parameter
Description
Alias
Name for identification of
measurement devices
Enable this device
Determines whether the
Fuel Save Controller should
take the measurement de-
vice into account in the con-
trol of the PV diesel hybrid
system
IP address
IP address of the Data Ac-
quisition Module
Data source priority
Use of the measured values
from the Fuel Save Con-
troller in the event of a com-
munication connection fail-
ure
Assign measurement
Overview of the activated
points
devices, e.g. PV inverters
Requirement:
☐ You must be logged in as Installer.
☐ You must have performed all necessary settings in the area External measurement devices in the menu
Measurement devices general configurations 55.
60
FSC20-BA-xx-20
Value
Explanation
Yes
The Fuel Save Controller
takes the measurement de-
vice into account.
No
The Fuel Save Controller
does not take the measure-
ment device into account.
172.16.0.0 to
The IP address of the
172.17.255.2
Data Acquisition Module is
55
defined during commission-
ing.
Single source
Connection to the device
carrying out the measure-
ments is disabled. Only the
measured values from the
Fuel Save Controller are
used.
Second source
Connection to the device
carrying out the measure-
ments is enabled. The val-
ues communicated by the
device have priority. If com-
munication fails, the mea-
sured values from the
Fuel Save Controller are
used.
Measurement
Connection to the device
priority
carrying out the measure-
ments is enabled. The val-
ues measured by the
Fuel Save Controller have
priority. In case of measure-
ment failure, the values
communicated by the de-
vice are used.
Via the button [Show devices], a menu is called up in which
devices can be activated or deactivated for the selected mea-
surement device. Furthermore, the devices that are connected
to the digital inputs of the Data Acquisition Module are config-
ured via this menu.