11.2

Error table

Classification No.
-
0
System
E004
errors
E005
E006
E007
Pump errors
E010
Motor errors E020
E021
E023
E025
E026
Module
E030
errors
E031
E032
E033
E035
Communica-
E050
tion errors
E051
E052
Electronics
E070
errors
E071
Installation and operating instructions LRE-JRE
Error
Cause
No error
Undervoltage
Mains overloaded
Overvoltage
Mains voltage too high
2-phase operation
Missing phase
Generator operation
The flow is driving the
(flow in flow direction)
pump impeller; electrical
current is being fed back
to the mains
Blocking
Shaft is mechanically
blocked
Excess winding tem-
Motor overloaded
perature
Motor ventilation limited Provide unobstructed air
Water temperature too
high
Motor overload
Duty point outside of
duty chart
Deposits in the pump
Short circuit/earth
Motor or module defec-
leakage
tive
Faulty contact
Module has no contact to
motor
Winding interrupted
Motor defective
WSK or PTC inter-
Motor defective
rupted
Excess module tem-
Limited air supply to
perature
module heat sink
Excess hybrid/power
Ambient temperature too
section temperature
high
Intermediate circuit
Voltage fluctuations in
undervoltage
the mains
Intermediate circuit
Voltage fluctuations in
overvoltage
the mains
DP/MP: multiple
Multiple instances of
instances of same
same identity
identity
BMS communication
Bus communication
time-out
interrupted or timed out
Cable break
Impermissible DP/MP
Different pumps
combination
DP/MP communication
Cable MP communication
time-out
defective
Internal communica-
Internal electronics error
tion error (SPI)
EEPROM error
Internal electronics error
Remedy
Check electrical installation
Check electrical installation
Check electrical installation
Check the setting, check sys-
tem for proper operation
CAUTION! Prolonged opera-
tion can cause damage to the
module
If the blocking has not been
removed after 10 s, the pump
switches off;
Check shaft for ease of move-
ment
Contact customer service
Allow motor to cool off, check
settings, check/correct duty
point
access
Lower water temperature
Check/correct the duty point
Contact customer service
Contact customer service
Contact customer service
Contact customer service
Contact customer service
Provide unobstructed air
access
Improve room ventilation
Check electrical installation
Check electrical installation
Reallocate master and/or slave
(see Section 9.2 on page 82)
Check cable connection to
building automation
Contact customer service
Check cable and cable connec-
tions
Contact customer service
Contact customer service
English
Error type
HV
AC
C
A
C
A
C
A
F
F
A
A
B
A
B
A
A
A
A
A
B
A
B
A
B
A
F
D
F
D
S
S
F
F
F
F
S
S
A
A
A
A