Annex 1: Extended storage checklist
Applicable to: Large fans with metal impellers, not supplied in cartons, should be stored so that:-
Impellers must be rotated minimum 10 turns once a month.
Motor insulation tested every 3 months.
Motor anti-condensation heater energized, if fitted.
Storage must not exceed 1 year, without review by supplier / manufacturer for possible damage to motor, bearings, grease.
Regular inspection and check list to be completed.
Project ID:
Fan ID:
Fan Code:
Fan ATEX Code:
Fan Serial No:
Item
Action
Visual inspection: environment safe,
S1
no damage, no corrosion
Rotate motor / impeller shaft
S2
Minimum 10 turns
Motor Insulation test
S3
Values M ohm
Motor Anti-Condensation heater on -
S4
if fitted
Review with supplier, if storage
beyond 1 year, to assess need for
S5
inspection of motor, bearings, grease,
belts, to assess for damage and
possible replacement.
Competent Inspector identifed.
S6
Refer IEC EN 60079-14
IEC EN 14986 Annex D: identifies "Storage damage" as potential hazard. Regular inspection by competent personnel avoids / reduces this hazard.
Annex 2. Fixing Torque
Annex 2.1: Typical bolt fixing torque
TORQUE SETTINGS ( Nm )
Electrical
Bolt size
Terminals
Metric
BRASS
M 2
0.14
M 2.5
0.29
M 3
0.5
M 4
1.2
M 5
2.2
M 6
3.9
M 8
9
M 10
17
M 12
M 14
M 16
M 18
M 20
M 22
M 24
M 27
M 30
Frequency
1
Storage maintenance schedule
Date
1 month
Sign
Date
1 month
Sign
Date
3 months
Sign
Date
3 months
Sign
Date
1 year
Sign
Fixings
STAINLESS
STAINLESS
STEEL
STEEL
STEEL
A2 - 70
A2 - 80
8.8
---
---
0.33
---
---
0.7
0.9
1.2
1.2
2.1
2.7
2.7
4.1
5.4
5.4
7.1
9.3
9.3
17.5
22
22
34
44
45
59
76
77
91
121
125
140
187
190
---
---
270
273
364
380
---
---
515
472
659
655
682
909
1000
930
1240
1350
Client:
Motor ATEX Code:
Motor Serial No:
2
3
4
5
6
35
7
8
9
10
11
12
loading

Este manual también es adecuado para:

ThgtTgt atex