• The system was designed for a certain duty point (full load point, cal-
culated maximum heating capacity requirement). During commis-
sioning, the pump output (delivery head) is to be set according to the
duty point of the system.
• Works settings do not comply with the output required for the sys-
tem. It is determined with the help of the pump curve diagram for the
selected pump type (from catalogue/data sheet).
CAUTION! Caution – material damage!
If the volume flow is too low, it can cause damage to the mechani-
cal seal.
• Ensure that the minimum volume is not less than 10% of the max-
imum volume flow.
Control (p-c/(p-v:
Setting (Fig. 38) (p-c
1
Duty point on
Draw from duty point
maximum pump
towards the left. Read
curve
off setpoint Hs and set
the pump to this value.
2
Duty point
Draw from duty point
within the con-
towards the left. Read
trol range
off setpoint Hs and set
the pump to this value.
Adjustment
H
, H
min
range
see pump curve
(in catalogue, select or
online)
NOTE
Alternatively, the manual control mode (Fig. 39) or the PID operating
mode can also be set.
Manual control mode:
The "manual control mode" deactivates the control in the module.
The speed of the pump is kept to a constant value and set internally
using the rotary knob.
The speed range depends on the motor power.
PID control
By selecting a good combination of individual control portions, the
operator can ensure fast reacting, constant control without lasting
setpoint deviations.
Control
Factory setting Setting range
portion
P
0.5
I
0.5 s
D
0 s
(= deactivated)
The control direction is determined by the leading sign of the P por-
tion.
(p-v
Draw from duty point
towards the left. Read
off setpoint Hs and set
the pump to this value.
Move to max. pump
curve along control
curve, then horizontally
to the left, read set-
point Hs and set the
pump to this value.
H
, H
max
min
max
see pump curve
(in catalogue, select or
online)
-30.0 ...
-2.0
-1.99 ... -0.01
0.00
...
1.99
2.0
...
30.0
10 ms ... 990 ms
1 s
... 300 s
0 ms ... 990 ms
1 s
... 300 s
Step
precision
0.1
0.01
0.01
0.1
10 ms
1 s
10 ms
1 s