FLUE EXHAUST CONNECTION

MOD. INOVA L24 MC W TOP-U/IT
The boiler is envisaged being connected to a chimney and/or a flue pipe; the combustion fumes can also be
discharged directly outside.

CONNECTION TO THE CHIMNEY

The joining to the chimney or flue pipe must be made with a smoke conduit having the following features:
of being sealed airtight, as with the connection to the chimney itself;
of being of suitable material;
of being connected within sight;
of having changes in direction, not more than 3 no., which must be carried out with internal angles
greater than 90° and with the use of curved elements;
of not having any intercepting devices;
of having the axis at the entrance of the terminal section perpendicular to the opposite internal wall of
the chimney;
of being firmly fixed and sealed at the entrance, without protruding beyond the inner walls of the
chimney;
of receiving preferably one boiler only;
of observing the local regulations in force.
WARNING:
This unit is fitted with a Flue Control device to control flue draught. This is tripped when there is a risk
of combustion fume backflow. This device must never be deactivated. If combustion fumes re-enter
the room they may cause chronic or acute intoxication and can be fatal. If the Flue Control device is
changed use only original spare parts. If the device trips repeatedly check for proper fume outflow
via the chimney flue and contact a Lamborghini Service Centre.
NO
Flue pipe or
chimney
YES
Ø 140 mm
H max. 2500 mm
4
3%
H*= useful height
43