FLUE EXHAUST CONNECTION
The boiler is envisaged being connected to a chimney and/or a flue pipe; the combustion fumes can also be
discharged directly outside.
The joining to the chimney or flue pipe must be made with a smoke conduit having the following features:
● of being sealed airtight, as with the connection to the chimney itself;
● of being of suitable material;
● of being connected within sight;
● of having changes in direction, not more than 3 no., which must be carried out with internal angles
greater than 90° and with the use of curved elements;
● of not having any intercepting devices;
● of having the axis at the entrance of the terminal section perpendicular to the opposite internal wall of the
chimney;
● of being firmly fixed and sealed at the entrance, without protruding beyond the inner walls of the chimney;
● of receiving preferably one boiler only;
● of observing the local regulations in force.
WARNING:
This unit is fitted with a Flue Control device to control flue draught. This is tripped when there is
a risk of combustion fume backflow. This device must never be deactivated. If combustion fumes
re-enter the room they may cause chronic or acute intoxication and can be fatal. If the Flue
Control device is changed use only original spare parts. If the device trips repeatedly check for
proper fume outflow via the chimney flue and contact a Lamborghini Service Centre.
NO
Flue pipe or
chimney
YES
Ø 130 mm *
* = VELA X N 24
3%
H max. 2500 mm
4
36