Technical Specifications - baltur TBG 85ME Manual De Instrucciones

Ocultar thumbs Ver también para TBG 85ME:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 23

TECHNICAL SPECIFICATIONS

HEATING CAPACITY
OPERATION
NOx EMISSIONS
MOTOR
ABSORBED ELECTRICAL POWER*
LINE FUSE
IGNITION TRANSFORMER
VOLTAGE
PROTECTION RATING
FLAME DETECTOR
NOISE**
WEIGHT
NATURAL GAS (G 20)
FLOW RATE
PRESSURE
*)
Total absorption at start with ignition transformer on.
**) Noise levels measured in the laboratory of the manufacturer with burner running on test boiler, at maximum rated heating capacity.
STANDARD ACCESSORIES
BURNER COUPLING FLANGE
INSULATING GASKET
STUD BOLTS
HEXAGONAL NUTS
FLAT WASHERS/
TECHNICAL AND FUNCTIONAL SPECIFICATIONS
Two-stage progressive / modulating output operation.
Gas adjustment using the butterfly valve controlled by the step
servomotor electronically controlled.
Combustion head with partial recycling of exhaust gases at low
NOx emissions (class II).
High fan output, low electrical absorption, low noise.
Ambidextrous hinge opening for easy access to the combustion
head when burner is installed.
Airflow adjustment with linear opening shutter driven by a step
servomotor electronically controlled.
Closing of air shutter in pause.
TBG 85ME
MAX kW
850
MIN
kW
170
Two-stage progressive / modulating burner
mg/kWh
kW
1.1
r.p.m.
2800
kW
1.20
A 400 V
6
IP 40
dBA
73
kg
78
MAX m³n/h
85.5
MIN
m³n/h
17
MAX mbar
TBG 85ME
2
1
No. 4 M 12
No. 4 M 12
No. 4 Ø 12
Control panel prepared for connection by plugs/sockets
(supplied) with 4 and 7 poles.
Control panel with protection rating IP55.
Sliding coupling flange to the generator, to adapt the
protuberance of the head to various types of heating generators.
High modulation ratio 1:5.
Gas train exit possibility at the top or at the bottom.
4 / 20
0006081531_201203
TBG 120ME
TBG 150ME
1200
1500
240
300
< 120 (Class II EN 676)
1.5
2.2
2800
2800
1.60
2.40
10
10
26 kV - 40 mA – 230 V / 50 Hz
3N ~ 400 V ±10%- 50 Hz
IONISATION PROBE
75.5
79
87
91
120.7
150.9
24.1
30.2
500
TBG 120ME
TBG 150ME
2
2
1
1
No. 4 M 12
No. 4 M 12
No. 4 M 12
No. 4 M 12
No. 4 Ø 12
No. 4 Ø 12
TBG 210ME
2100
400
3
2800
3.2
16
85
94
211.2
40.3
TBG 210ME
2
1
No. 4 M 12
No. 4 M 12
No. 4 Ø 12