4. Electrical work
Confirmation procedure
Manual vane angle
M-NET address
Identify unit Check button
Input display:
Cur.
Address
Check
F1
F2
F3
F4
Manual vane angle
M-NET address
The air conditioner with the
vane pointing downward is
the target air conditioner.
Input display:
F1
F2
F3
F4

5. Installing the grille

Fig. 5-1
Fig. 5-2
10
Select the "M-NET address" for
the units to whose vanes are to be
fixed, with the [F2] or [F3]
button.
Press the [F4] button to confirm the
unit.
After pressing the [F4] button,
wait approximately 15 seconds,
and then check the current state
of the air conditioner.
→ The vane is pointing downward.
→ This air conditioner is displayed
on the remote controller.
→ All outlets are closed. → Press
the [RETURN] button and contin-
ue the operation from the begin-
ning.
→ The messages shown to the
left are displayed. → The target
device does not exist at this refrig-
erant address.
• Press the [RETURN] button to re-
turn to the initial screen.
Manual vane angle
There is no response from
the target device.
Confirm the state of the air
conditioner.
Input display:
F1
F2
F3
F4
5.1. Checking the contents (Fig. 5-1)
• This kit contains this manual and the following parts.
Accessory name
Grille
Screw with captive washer
Gauge
Fastener
Screw
Screw
i-see sensor corner panel
5.2. Preparing to attach the grille (Fig. 5-2)
• With the gauge
supplied with this kit, adjust and check the positioning of the
unit relative to the ceiling. If the unit is not properly positioned relative to the ceil-
ing, it may allow air leaks or cause condensation to collect.
• Make sure that the opening in the ceiling is within the following tolerances:
860 × 860 - 910 × 910
• Make sure that A is performed within 17-22 mm. Damage could result by failing
to adhere to this range.
Main unit
Ceiling
Gauge
(inserted into the unit)
Ceiling opening dimensions
Change the "M-NET address" to
the next number.
• Refer to step
to change the
"M-NET address" and continue
with the confirmation.
Q'ty
Remark
1
950 × 950 (mm)
4
M5 × 0.8 × 25
1
(Divided into four parts)
3
4
4 × 8
1
4 × 12
1
for PLP-6BAE