Installing The Grille; Selection Of The Air Outlets - Mitsubishi Electric Mr.Slim PLA-RP BA Serie Manual De Instalación

Ocultar thumbs Ver también para Mr.Slim PLA-RP BA Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 74

. Installing the grille

Fig. -1
Fig. -
Fig. -3
Fig. 9-4
4-directional
1 pattern: initial setting
Blowout direction
patterns
2-directional
6 patterns:
2 air outlet fully closed
Blowout direction
patterns
Fig. -5
?
3-directional
4 patterns:
one air outlet fully closed
Table 1
A Main unit
B Screw with captive washer
.1. Checking the contents (Fig. -1)
• This kit contains this manual and the following parts.
Accessory name
Grille
1
Screw with captive washer
2
Gauge
3
Fastener
4
Screw
5
Screw
6
Wireless remote controller
7
i-see sensor corner panel
8
.. Preparing to attach the grille (Fig. -)
• With the gauge 3 supplied with this kit, adjust and check the positioning of the
unit relative to the ceiling. If the unit is not properly positioned relative to the ceil-
ing, it may allow air leaks or cause condensation to collect.
• Make sure that the opening in the ceiling is within the following tolerances:
860 × 860 - 910 × 910
• Make sure that A is performed within 17-22 mm. Damage could result by failing
to adhere to this range.
A Main unit
B Ceiling
C Gauge 3 (inserted into the unit)
D Ceiling opening dimensions
..1. Removing the intake grille (Fig. -3)
• Slide the levers in the direction indicated by the arrows 1 to open the intake
grille.
• Unlatch the hook that secures the grille.
* Do not unlatch the hook for the intake grille.
• With the intake grille in the "open" position, remove the hinge of the intake grille
from the grille as indicated by the arrows 2.
9.2.2. Removing the corner panel (Fig. 9-4)
• Remove the screw from the corner of the corner panel. Slide the corner panel as
indicated by the arrow 1 to remove the corner panel.
[Fig.9-3] [Fig.9-4]
A Intake grille
B Grille
C Intake grille levers
D Grille hook
E Hole for the grille's hook
F Corner panel
G Screw
H Detail

.3. Selection of the air outlets

For this grille the discharge direction is available in 11 patterns. Also, by setting the
remote controller to the appropriate settings, you can adjust the air-flow and speed.
Select the required settings from the Table 1 according to the location in which you
want to install the unit.
1) Decide on the discharge direction pattern.
2) Be sure to set the remote controller to the appropriate settings according to the
number of air outlets and the height of the ceiling on which the unit will be in-
stalled.
Note:
For 3 and -directional, please use the air outlet shutter plate (option).
9.4. Installing the grille
9.4.1. Preparations (Fig. 9-5)
• Install the 2 enclosed screws with washer 2 in the main unit (at the corner drain
pipe area and at the opposite corner) as shown in the diagram.
Q'ty
Remarks
1
950 × 950 (mm)
4
M5 × 0.8 × 25
1
(Divided into 4 parts)
3
4
4 × 8
1
4 × 12
1
for PLP-6BALM, PLP-6BALME
1
for PLP-6BAE, PLP-6BALME
17

Hide quick links:

Tabla de contenido
loading

Tabla de contenido