Range Rated - Ferroli ENERGY TOP B 80 Instrucciones De Uso

Ocultar thumbs Ver también para ENERGY TOP B 80:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
ENERGY TOP B
6.
Undo the screws "C" and remove fan "D" (fig. 56 - only model ENERGY TOP B 125
- 250)
3
C
fig. 56 - model ENERGY TOP B 125 - 250
7.
Undo the fixing screws "E" (fig. 57 model ENERGY TOP B 80 - 160 and fig. 58
model ENERGY TOP B 125 - 250) and remove the gas valve.
fig. 57 - model ENERGY TOP B 80 - 160
E
G
fig. 58 - model ENERGY TOP B 125 - 250
8.
Replace the gas nozzle "F" (see fig. 57 for the model ENERGY TOP B 80 - 160 and
fig. 58 the model ENERGY TOP B 125 - 250) with the one contained in the con-
version kit, positioning it inside the seal "G" . Refit the parts and check their tight-
ness.
9.
Modify the parameter for the type of gas:
put the boiler in standby mode
press the DHW buttons (details 1 and 2 - fig. 1) at the same time for 10 sec-
onds: the display shows "P01" flashing.
Press the DHW buttons (details1 and 2 - fig. 1) toset parameter 00 (for use
with natural gas ) or 01 (for use with LPG).
press the DHW buttons (details 1 and 2 - fig. 1) together for 10 seconds. The
boiler will return to standby mode
10. Apply the label, contained in the conversion kit, near the dataplate.
11. Using a combustion analyser connected to the boiler fume outlet, make sure the
CO
content in the fumes, with the boiler operating at max. and min. output, com-
2
plies with that given in the technical data table for the corresponding type of gas.
D
2
3
1
2
C
1
C
F
G
E
F
cod. 3541H060 - Rev. 02 - 04/2018
TEST mode activation
Press the heating buttons +/- (details 3 and 4 - fig. 1) together for 5 seconds to activate
TESTmode. The boiler lights at the maximum heating power (Range Rated) set as de-
scribed in the following section.
The heating symbol (detail 13 - fig. 1) and DHW symbol (detail 9 - fig. 1) flash; the heat-
ing power will appear alongside.
fig. 59 - TEST mode (heating power = 100%)
To deactivate Test mode, repeat the activation sequence.
The TEST mode is automatically disabled in any case after 15 minutes.
Only for model ENERGY TOP B 160 - 250
In TEST mode, press the button (detail 7 - fig. 1) to obtain the following operation:
Top boiler shell on; bottom boiler shell off.
Top boiler shell off; bottom boiler shell on.
Top boiler shell on; bottom boiler shell on.
Heating Capacity Adjustment (RANGE RATED)
This is a "RANGE RATED" boiler (according to EN 483) and can be adjusted
A
to the system's thermal requirement by setting the maximum heating capacity
for operation in heating mode, as follows:
Put the boiler in TEST mode (see sec. 4.1).
Press the heating buttons (details 3 and 4 - fig. 1) to increase or decrease the pow-
er (min. = 00 - max. = 100). See the diagram "Heating Capacity Adjustment"
(fig. 60).
Press the reset button (detail 8 - fig. 1) within 5 seconds and the maximum heating
capacity will remain that just set. Exit TEST mode (see sec. 4.1).
THE HEATING CAPACITY ADJUSTMENT THUS SET ENSURES KEEPING
A
OF THE EFFICIENCY VALUES DECLARED ON cap. 5.4
Heating power adjustment diagram
A = kW - B = Electronic Board Parameter
B
100
90
80
70
60
50
40
30
20
10
0
0
20
40
60
80
100
4.2 Start-up
B
Checks to be made at first lighting, and after all maintenance operations that
involved disconnection from the systems or an operation on safety devices or
parts of the boiler:
Before lighting the boiler
Open any on-off valves between the boiler and the systems.
Check the tightness of the gas system, proceeding with caution and using a soap
and water solution to detect any leaks in connections.
Check correct prefilling of the expansion tank (ref. sec. 5.4).
Fill the water system and make sure all air contained in the boiler and the system
has been vented, by opening the air vent valve on the boiler and any vent valves on
the system.
Fill the condensate trap and check correct connection of the condensate elimination
system.
Make sure there are no water leaks in the system, DHW circuits, connections or boiler.
Check correct connection of the electrical system and efficiency of the earthing system
Make sure the gas pressure value for heating is that required.
Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler

RANGE RATED

eco
reset
comfort
120
140
160
180
200
220
A
fig. 60
EN
240
260
83
Tabla de contenido
loading

Este manual también es adecuado para:

Energy top b 160Energy top b 125Energy top b 250

Tabla de contenido