Check the cut-in pressure during draining
5.
Check the cut-in and cut-out pressure of the compressor.
(Factory setting)
–
The compressor cuts in at P
–
The compressor cuts out at P
Check make-up "On"
6.
If necessary, check the make-up display value in the app.
–
Automatic make-up is switched on at a filling level of 8 %.
–
If the cut-in point is reached, automatic make-up is to be deactivated.
Check low water "On"
7.
Drain more water from the vessel.
8.
Check the display value of the "Low water" filling level message in the app.
Ensure that the vessel is completely empty for this purpose.
–
Low water "On" is displayed in the app or as an LED on the device
once a minimum filling level of 5% is reached.
9.
Switch to Stop mode.
10. Completely disconnect the system from the power supply.
Note!
The membrane is defective if, with the vessel empty, air flows
continuously out of the draining valve.
-> Replace vessel
Switch on the device
11. Reconnect the power supply to the system.
12. Ensure that the automatic make-up is switched off or shut off.
13. Perform a calibration to calibrate the weight measuring cell by (Setting
Maintenance Calibration)
14. Change to automatic mode and wait until the compressor has reached its
cut-off pressure.
15. Slowly open the cap valves upstream of the vessel and secure them against
unauthorised closing.
16. Activate automatic make-up.
Check low water "Off"
17. Check the display value for the low water "Off" filling level message in the
app.
–
Low water "Off" is displayed in the app or as an LED on the device
once a filling level of 8% is reached.
Check make-up "Off"
18. If necessary, check the make-up display value in the app.
–
Automatic make-up is deactivated at a filling level display of 12 %.
Maintenance is completed.
Note!
Alternatively, the functioning of the individual components (solenoid valve,
compressor) can be checked by switching in manual mode. (Setting
Maintenance Manual mode).
Note!
If no automatic make-up is connected, manually fill the vessel with water
up to the noted filling level.
Note!
The setting values for pressure maintenance, filling levels and make-up
can be found in the chapter Default settings, 9.3 "Default settings ",
28.
+ 0.3 bar.
0
+ 0.4 bar.
0
Reflexomat RSC Smart — 08.01.2024-Rev. A
10.3
Cleaning the vessel
CAUTION
Risk of injury due to pressurised liquid
Injuries can occur during maintenance work if the installation of the
connections is incorrect because pressurised condensate can suddenly
escape.
•
Ensure proper connections for the draining of condensate.
•
Wear suitable personal protective equipment (safety gloves and safety
goggles, for example).
•
Ensure that the system is depressurised.
Regularly clean the vessel to remove condensate. The cleaning intervals depend
on the local operational conditions.
Vessel with replaceable membrane
1
Record the level display value shown on the controller.
2.
Press "Manual" at the control panel to switch the controller into Manual
mode.
3.
Remove the silencer from the "PV" overflow solenoid valve.
4.
Install a suitable hose in the "PV" overflow solenoid valve to drain
condensate.
5.
Slowly open the "PV" overflow solenoid valve.
–
If the pressure in the system circuit drops significantly, the water must
be made up manually.
–
If the "PV" overflow solenoid valve discharges more than 5 litres of
water or condensate, you must check the membrane for rupture.
•
The vessel must be replaced if the membrane has ruptured.
6.
Close the "PV" overflow solenoid valve if the display indicates a 100 % level.
7.
Start the "CO" compressor to build up pressure.
–
If water had to be manually made up during draining of the
condensate, you must monitor the pressure build up. At excessive
pressure rise, drain water from the system circuit accordingly.
8.
Switch the controller into Automatic mode when the recorded level is
displayed at the controller.
9.
Remove the hose from the "PV" overflow solenoid valve and fit the silencer.
10. Maintenance is completed.
10.3.1 Cleaning the dirt trap
Regularly clean the "ST" dirt trap. The cleaning intervals depend on the local
operational conditions.
1
"ST" dirt trap
1.
Switch to Stop mode.
–
Press "Stop" on the controller's operator panel.
2.
Close the ball valves upstream and downstream of the "ST" (1) dirt trap.
3.
Slowly unscrew the dirt trap insert (2) from the dirt trap in order for the
residual pressure to escape from the pipeline segment.
4.
Pull the mesh from the dirt trap insert and rinse it with clear water. Use a soft
brush for cleaning.
5.
Re-insert the mesh into the dirt trap insert, check the gasket for damage, and
screw the dirt trap insert back into the housing of the "ST" (1) dirt trap.
6.
Re-open the ball valves upstream and downstream of the "ST" (1) dirt trap.
7.
Switch to Automatic mode.
–
Press "Auto" on the controller's operator panel.
Note!
Clean all other installed dirt traps (in the Reflex Fillset, for example).
Maintenance