Reflex Reflexomat RSC Smart Manual De Instrucciones Original página 28

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 50
Controller
9.2
Operator panel
1
Auto button/LED
The Auto button starts operation after commissioning or from stop
mode
The Auto LED illuminates green in Automatic mode
The Auto LED is off in stop mode
2
Pressure LED
The Pressure LED comes on in automatic mode
The Pressure LED flashes if there is a fault or during increasing
and decreasing of the pressure
3
Level LEDs
The level LEDs indicate the filling level in the vessel.
High water 3.1
Auto mode 3
Low water 3.3 (make-up requirement)
4
Display
Pressure and level of the system are displayed here
In the event of a fault, the error code is shown on the display
5
Stop button/LED
The stop button is for entering new values in the controller and for
manual mode (maintenance mode)
The Stop LED lights up in yellow
6
Service button/LED
Warning and fault messages are acknowledged with the Service
button
The Service LED lights up in the event of a warning message
The Service LED flashes in the event of a fault message
9.3
Default settings
The device controller is shipped with the following default settings. Other settings
must be made during assisted commissioning using the Reflex Control Smart app.
Default settings
Parameter
Setting
Next maintenance
12 months
Floating contact
YES
Make-up
Make-up "ON"
8 %
Make-up "OFF"
12 %
Maximum make-up
0 Litres
quantity
Maximum make-up time
30 minutes
Maximum make-up cycles
6 cycles
within 2 hours
28 — English
Comment
Time left to the next due
maintenance.
 9.4 "Messages",  29.
Only when using a water meter.
Reflexomat RSC Smart — 08.01.2024-Rev. A
Parameter
Setting
Pressure maintenance
Compressor "ON"
P
+ 0.3 bar
0
Compressor "OFF"
P
+ 0.4 bar
0
"Compressor run time
180 minutes
exceeded" message
Outward flow solenoid
P
+ 0.4 bar
0
valve "CLOSE"
Outward flow solenoid
P
+ 0.5 bar
0
valve "OPEN"
PSv – 0.3 bar
Maximum pressure
Filling levels
Low water "ON"
5 %
Low water "OFF"
12 %
Solenoid valve in overflow
90 %
pipe "CLOSED"
Comment
Differential pressured added to
the "P
" minimum operating
0
pressure.
Differential pressured added to
the "P
" minimum operating
0
pressure.
The message is displayed in the
app after compressor running of
180 minutes.
Differential pressured added to
the "P
" minimum operating
0
pressure.
Differential pressured added to
the "P
" minimum operating
0
pressure.
Differential pressure as the
triggering pressure of the
response pressure of safety
valve "PSv".
loading