Maintenance
ER
Alarm
Code
09
Filling level measurement
[1] Auto LED off
[4] Stop LED flashes
[5] Error LED flashes
[3] Level LED flashes
10
Maximum pressure
[1] Auto LED lights up
[2] Pressure LED flashes
[5] Error LED lights up
11
Make-up quantity
15
Make-up valve
Stop ˃ 4 hours
19
[4] Stop LED lights up
[5] Error LED flashes
20
Max. make-up quantity
21
Maintenance recommended
[1] Auto LED lights up
[5] Error LED lights up
24
Softening/demineralisation
10
Maintenance
CAUTION
Risk of burns
Escaping hot medium can cause burns.
Maintain a sufficient distance from the escaping medium.
Wear suitable personal protective equipment (safety gloves and
goggles).
DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
Ensure that the supply cable to the device is disconnected and secured
against being switched back on.
Ensure that the system is secured and cannot be reactivated by other
persons.
Ensure that installation work for the electric connection of the device is
carried out by an electrician, and in compliance with electrical locally
applicable electrical engineering regulations.
The device must be maintained annually.
The maintenance intervals depend on the local operational conditions.
An indication that the annual service is to be performed after the set device
operating time has elapsed is given in the form of a warning. The warning is also
displayed in the app. The maintenance interval must be reset using the app.
Use operating mode "manual mode" for maintenance  8.1.3 "Manual mode",
 27.
Injuries can occur during maintenance work if the installation of the connections is
incorrect because pressurised condensate can suddenly escape. Ensure proper
connections for condensate draining.
Wear suitable personal protective equipment (safety glasses and safety gloves, for
example).
Regularly clean the vessel to remove condensate. The cleaning intervals depend
on the local operational conditions.
30 — English
Causes
Controller receives incorrect signal from the
weight measuring cell.
Set value (P
-0.3 bar) exceeded:
Sv
Air side solenoid valve does not blow off.
Compressor runs continuously.
Specified make-up quantity has been exceeded
Severe water loss in the system.
Contact water meter measures without make-up
request
Device is in Stop mode for more than 4
hours.
Max. set make-up quantity exceeded
Maintenance interval exceeded.
Soft water capacity used up
Reflexomat RSC Smart — 08.01.2024-Rev. A
Remedy
Check the plug connection at the weight
measuring cell.
Check the functioning of the weight
measuring cell.
Check the cable for damage.
Check the set values.
Check system-side water connection.
Check functioning of air side solenoid valve.
Clean the silencer of the air-side solenoid
valve.
Check the compressor relay.
Check system for leakage.
Check system for leakage.
Clean make-up valve.
Replace make-up valve (if necessary).
Reset using the SmartControl app.
Set make-up quantity correctly.
Carry out maintenance.
Reset maintenance counters in the app.
Replace the cartridge (Fillsoft).

Note!
Maintenance tasks must only be carried out by specialist personnel or
Reflex Customer Service.
10.1
Maintenance schedule
The maintenance schedule is a summary of maintenance tasks to be carried out
regularly.
Activity
Check for leak tightness.
Compressor.
Screw connections of the
compressed air connections.
Check switching points.
Cut-in pressure compressor.
Low water.
Make-up with water.
10.2
Checking switching points (during vessel draining)
Prerequisite for checking the switching points are the following correct settings:
Minimum operating pressure P
measuring cell",  24.
Filling level measurement in the primary vessel.
Preparation
1.
Switch to Automatic mode.
2.
Close the cap valves upstream of the vessel.
3.
Record the indicated filling level (value in %) from the app.
4.
Drain the water from the vessel.

Note!
During vessel draining, continuously monitor the filling level and pressure
values in the app and check the switching points.
Alarm reset
"Service"
"Service"
"App"
Interval
x
x
Annually
x
Annually
,  6.3.3 "Installation of the weight
0
-
-
-
-
-
loading