Mounting
2.4
Limitations on use
The flame detector is not approved for use in oxygen-enriched
atmospheres.
As the flame detector responds to flame, it cannot be used in locations
where flare stacks and other open flames are within its field of view without
triggering false alarms.
The flame detector may be obscured by extremely dense fog, smoke or
other airborne particulates.
Arc welding should not take place within 10 m of the flame detector when
using the highest sensitivity setting.
2.5
Approvals
For information - certificate numbers may change.
Authority/
Parameter
Standard
Hazardous area certifica-
ATEX
tion
Hazardous area certifica-
NEC 505
tion
Hazardous area certifica-
NEC 500
tion
Hazardous area certifica-
IECEx
tion
American fire service list-
FM
ing
European fire service list-
FM
ing
CE Marked (Emissions)
Element
CE Marked (Immunity)
FM
IEC 61508
Exida
Class Guideline
DNV-GL
8
Approval
Certificate
II 2 G Ex db IIC T4 Gb IP67 FM21ATEX0012X
Class 1 Zone 1 AEx db IIC
T4
Class 1 Div 1, Groups B, C,
D T4
IECEx FMG
Ex db IIC T4 Gb IP67
21.0009X
FM23FPCA0002 &
Class 3260, 3810
FM23FPUS0065
EN 54 Part 10 2002
2809-CPR-E0019
EN 61000-6-3:2007
A1:2011
EN 50130-4 2011 A1:2014
Certified SIL 2 Capable
DNVGL-CG-0339
Authority/
Parameter
Standard
Ingress Protection
FM
Further standards can be found in the EU DoC at the end of this document.
2.6
Explanation of type-identifying marking and
symbols
The flame detector is fitted with a label that shows the certification and
conditions within which it can operate.
The following label is an example only.
FLAME 1750
TYPE:
SERIAL No:
3260
EN54-10
YEAR:
2809-CPR-EXXXX
Dräger Safety AG & Co. KGaA
ENTRY:
Angle of reception 90º
Revalstraße 1
M25
½"NPT
Single
23560 Lübeck, Germany
M20
¾"NPT
Dual
Class 3 High & Standard Sensitivity
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT
WARNING: REFER TO FLAME 1750 INSTRUCTIONS FOR USE BEFORE INSTALLING OR MAINTAINING THIS UNIT
3
Mounting
3.1
Prerequisites for installation
When selecting a mounting position for the flame detector, observe the
following:
Ensure that the flame detector has an unobstructed view of the areas to be
protected.
Ensure that the mounting position is free from vibration or movement.
Ensure that the mounting position has sufficient support for the flame
detector and allows for horizontal adjustment.
Ensure that the flame detector is aimed downwards by at least 10° to 20°.
This will reduce the build-up of contaminants on the lens.
Ensure that the flame detector is protected from sources of impact damage
and from being knocked out of alignment.
Install the flame detector as far away as possible from local sources of
possible electrical interference, such as X-rays, RF (radio frequency)
interference or electrostatic discharge.
Approval
Certificate
IP67, NEMA Type 6P
0158
II 2 G Ex db IIC T4 Gb
TYPE 6P, IP67
Class I DIV 1 GROUPS B,C,D T4
AMBIENT: -60ºC to +85ºC
Class I Zone 1 AEx db IIC T4 Gb
Ambient: -50ºC to +85ºC
FM21ATEXXXXXX
IECEx FMG 21.XXXXX
Maximum Voltage: 32VDC
Do not repair flame paths contact manufacturer
Maximum Current: 700mA
Seal conduit within 18" of enclosure entrance
Instructions for use
|