Button to switch between blower rpm or % of max output, as well as limit the max output of the blower.
Button to open the setpoint screen where number of setpoints are entered.
Button to view the status of I/O inputs and outputs.
The screenshot shows that operator does not have the right to switch between remote or
local control, i.e. whether the trim handler is controlled from the operator panel or via the di-
gital inputs on the PLC. If there is a green tick, the operator has the right to switch between
remote or local control.
The screenshot shows that the operator does not have the right to adjust the setpoint(s). If
there is a green tick, the operator has the right to adjust the setpoint(s).
The screenshot shows that the operator does not have the right to start and stop the trim
handler via the operator panel.
8
Settings - User Admin
User Admin is password protected.
When the user is logged in as Admin, the screen is displayed with a blue
border.
It is the Admin's task during installation of the trim handler to select the ope-
rating mode of the trim handler and how the trim handler is to be controlled.
This means that Admin is normally only used once during the installation of
the trim handler.
Replacing the frequency converter
If the frequency converter has been replaced, do the following:
•
log on as Admin
•
press the Kongskilde logo in the top right corner for at least 10 sec.
The Kongskilde logo changes to LOAD MOTORDATA and flashes
with white and red background respectively
•
press the flashing LOAD MOTOR DATA
•
a new page appears, where you press: Load Parameters to Drive,
which flashes with white and red background respectively
•
when the blue bar is at 100%, press Return, after which you return to
the Admin menu
The software is now downloaded to the frequency converter.
In case it is not possible to load the new data, the frequency converter is
not set up to communicate via the Profinet connection.