Emission And Immunity Levels - WEG CFW500 Manual Del Usuario

Ocultar thumbs Ver también para CFW500:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Installation and Connection

3.3.2 Emission and Immunity Levels

EMC Phenomenon
Emission:
Mains terminal disturbance voltage
Frequency range: 150 kHz to 30 MHz)
Electromagnetic radiation disturbance"
Frequency range: 30 MHz to 1000 MHz)
Immunity:
Electrostatic discharge (ESD)
Fast transient-burst
Conducted radio-frequency common
mode
Surges
Radio-frequency electromagnetic field
Definition of Standard IEC/EM 61800-3: "Adjustable Speed Electrical Power Drives
Systems"
Environments:
First Environment: environments that include domestic installations, as well as establishments
directly connected without intermediate transformer to a low-voltage power supply network
which supplies buildings used for domestic purposes.
Second Environment: includes all establishments other than those directly connected to a low-
voltage power supply network that supplies buildings used for domestic purposes.
Categories:
Category C1: inverters with a voltage rating less than 1000 V and intended for use in the First
Environment.
Category C2: inverters with a voltage rating less than 1000 V intended for use in the First
Environment, not provided with a plug connector or movable installations. They must be installed
and commissioned by a professional.
NOTE!
A professional is a person or organization familiar with the installation and/or
commissioning of inverters, including their EMC aspects.
Category C3: inverters with a voltage rating less than 1000 V and intended for use in the
Second Environment only (not designed for use in the First Environment).
24 | CFW500
Table 3.4: Emission and immunity levels
Basic
Standard
IEC/EN 61800-3
IEC 61000-4-2
IEC 61000-4-4
IEC 61000-4-6
IEC 61000-4-5
IEC 61000-4-3
Level
It depends on the inverter model on the
length of the motor cable. Refer to
B.3 on page 151
4 kV for contact discharge and 8 kV for air
discharge 8 kV
2 kV / 5 kHz (coupling capacitor) input cables
1 kV / 5 kHz control cables and remote HMI
cables
2 kV / 5 kHz (coupling capacitor) motor cables
0.15 to 80 MHz; 10 V; 80 % AM (1 kHz)
Motor, control and HMI cables
1.2/50 μs, 8/20 μs
1 kV line-to-line coupling
2 kV line-to-ground coupling
80 to 1000 MHz
10 V/m
80 % AM (1 kHz)
Table