7. Electrical work
Service menu
Test run
Input maintenance info.
Function setting
Check
Self check
Main menu:
Cursor
F1
F2
F3
F4
Fig. 7-11
Function setting
Ref. address
Grp.
Mode 1
Mode 2
Mode 3
Mode 4
Request:
Cursor
Cursor
F1
F2
F3
F4
Fig. 7-13
Function setting
Ref. address
Sending data
F1
F2
F3
F4
Fig. 7-15
Fig. 7-16
Fig. 7-18
Function setting
Ref. address
Unit No.
Grp./1/2/3/4/All
Monitor:
Cursor
Address
F1
F2
F3
F4
Fig. 7-12
Function setting
Unit # 1
Ref. address
Mode 7
Mode 8
Mode 9
Mode 10
Request:
Cursor
Cursor
F1
F2
F3
F4
Fig. 7-14
Fig. 7-17
B
Fig. 7-19
7.4. Function settings
7.4.1. By wired remote controller
1 (Fig. 7-11)
• Select "Service" from the Main menu, and press the [SELECT] button.
• Select "Function setting" with the [F1] or [F2] button, and press the [SELECT]
button.
2 (Fig. 7-12)
• Set the indoor unit refrigerant addresses and unit numbers with the [F1]
through [F4] buttons, and then press the [SELECT] button to confi rm the cur-
rent setting.
<Checking the Indoor unit No.>
When the [SELECT] button is pressed, the target indoor unit will start fan opera-
tion. If the unit is common or when running all units, all indoor units for the se-
lected refrigerant address will start fan operation.
3 (Fig. 7-13)
• When data collection from the indoor units is completed, the current settings
appears highlighted. Non-highlighted items indicate that no function settings
are made. Screen appearance varies depending on the "Unit No." setting.
4 (Fig. 7-14)
• Use the [F1] or [F2] button to move the cursor to select the mode number, and
change the setting number with the [F3] or [F4] button.
5 (Fig. 7-15)
• When the settings are completed, press the [SELECT] button to send the set-
ting data from the remote controller to the indoor units.
• When the transmission is successfully completed, the screen will return to the
Function setting screen.
7.4.2. By wireless remote controller (Fig. 7-16, Fig. 7-17, Fig. 7-18, Fig.
7-19)
1 Going to the function select mode
Press the
button between of 5 seconds.
(Start this operation from the status of remote controller display turned off.)
[CHECK] is lighted and "00" blinks. (Fig. 7-16)
Press the
button to set the "50".
Direct the wireless remote controller toward the receiver of the indoor unit and
A
press the
button.
2 Setting the unit number
Press the
button to set unit number A. (Fig. 7-17)
Direct the wireless remote controller toward the receiver of the indoor unit and
press the
button.
3 Select a mode
Press the
button to set Mode number B. (Fig. 7-18)
Direct the wireless remote controller toward the receiver of the indoor unit and
press the
button.
Current setting number:
4 Selecting the setting number
Use the
button to change the Setting number C. (Fig. 7-19)
Direct the wireless remote controller toward the receiver of the indoor unit and
press the
button.
C
5 To select multiple functions continuously
Repeat select 3 and 4 to change multiple function settings continuously.
6 Complete function selection
Direct the wireless remote controller toward the sensor of the indoor unit and press
the
button.
Note:
Make the above settings on units as necessary.
• Table 1 summarizes the setting options for each mode number.
• Be sure to write down the settings for all functions if any of the initial settings
has been changed after the completion of installation work.
1=1 beep (1 second)
2=2 beep (1 second each)
3=3 beep (1 second each)
11