CONNECTIONS
STANDBY
The STANDBY function allows the pump to be stopped remotely. If a dry contact or open collector
signal is received to the STANDBY inputs, the pump will cease operation as long as the signal is
present. The pump will also flash "STANDBY" on the operating display.
NOTE: The STANDBY function can be used to transfer operation to a secondary pump in the event of a primary pump
failure. An output relay on the primary pump is programmed for TRANSFER and Normally Closed. This relay provides an
input to the STANDBY function of the secondary pump, which is programmed identically to the primary pump. In the
event of a loss of power or an alarm event that shuts down the primary pump, the output relay on the primary pump
opens and activates the secondary pump.
Controller
Dry Contact Relay Output
Connection Terminals
Connection to a Dry Contact
• There is no polarity to observe.
• Connect relay to Standby (+), position #4 and Standby (–), position #5 on the top row.
Connection to an Open Collector output
• Polarity must be observed.
• Connect OC positive to Standby (+), position #4 on the top row.
• Connect OC common to Standby (–), position #5 on the top row.
1
2
3
Output
Output
Standby
Relay
Relay
1
1
Output
Output
4-20mA
Relay
Relay
3
3
11
12
13
S Series FW 4.01.02 US and Canada 800.683.2378, International 904.641.1666 www.stenner.com
continued
Pump
Input
4
5
6
7
4-20mA
Pulse/
Standby
0-10VDC
IN
PPM/Hall
+
+
(
)
(
)
(
signal)
+
(
signal)
signal
Leak
Leak
Flow
4-20mA
OUT
OUT
Detect
Detect
Detect
+
(
)
(
)
External
External
14
15
16
17
Controller
Open Collector Output
8
9
10
Hall
Signal
+
Common
12VDC
Flow
Flow
Detect
Detect
+
(
)
12VDC
18
19
20
71
Pump
Input
loading

Este manual también es adecuado para:

S30S40S50