CONTROL MODES MENU
4-20mA
page 3 of 3
NOTE: Signal alarms are non-latching and will clear automatically when the signal returns to specified operating range.
Alarms activate when settings are exceeded.
NAVIGATION
Moves up in a menu, toggles
between options, or increase a value
Holding the
or
button causes the numbers to change rapidly.
Continued from previous page
4-20mA
- Program Settings
- Alarm Settings
- Go to Main Menu
alarm activates when the
signal falls below the setting.
Select "Yes" to stop the pump in the
event of a low signal alarm. Select "No"
to allow the pump to continue running in
the event of a low signal alarm.
To 4-20mA menu
Select "No" to not enable the
high signal alarm and return to
the 4-20mA Control menu.
S Series FW 4.01.02 US and Canada 800.683.2378, International 904.641.1666 www.stenner.com
continued
Moves down in a menu, toggles
between options, or decreases a value
Alarm on Low Signal?
yes/no
Set low signal level. The
Low Signal Alarm
adjust
Stop Pump on L ALM??
yes/no
No
Alarm on High Signal?
yes/no
High Signal Alarm
adjust
Stop Pump on H ALM?
yes/no
To 4-20mA menu
Moves one step back in
a menu, when permitted
No
Yes
set
Select "No" to not enable the low signal alarm
Yes
and skip to the high signal Alarm Settings.
_ 3.0 mA
set
No
set
Yes
set
Yes
Select "Yes" to enable high signal alarm.
Set high signal level. The
alarm activates when the
21.0 mA
signal rises above the setting.
set
Select "Yes" to stop the pump in the
event of a high signal alarm. Select "No"
No
to allow the pump to continue running in
set
the event of a high signal alarm.
34
Sets a value in a menu
loading