Instructions
Designation system for the Optyma™ Plus range
OP - MPPM
028 VVL P01
1 2 3 4
5
1 Application
M = MBP
L = LBP
2 Package
Condensing unit family: P = Optyma™ Plus INVERTER
3 Refrigerant
P = R448A/R449A, R407A/F, R404A/R507
4 Condenser
M = Microchannel heat condenser
5 Swept volume
Displacement in cm
3:
Example 034 = 34 cm
6 Compressor platform
VVL = Scroll compressor with Inverter
7 Version
P01: Optyma™ Plus INVERTER
8 Voltage code
E = 400V/3-phase/50Hz compressor & 230V/1-phase fan
Technical data
Application
Code
Model
MBP
114X4302
OP-MPPM028VVLP01E
MBP
114X4316
OP-MPPM035VVLP01E
MBP
114X4334
OP-MPPM044VVLP01E
*PED Category for Group 2 fluid
© Danfoss | Climate Solutions | 2022.03
E
6
7
8
Version control
Optyma™ Plus INVERTER
IP level
Compressor technology
Control box (pre-wired E-panel)
Microchannel condenser
Fan speed controller*
Main switch (circuit breaker)
Supply monitoring relay
Filter drier (flare connections)
Sight glass
3
Crankcase heater
HP/LP adjustable pressostat
Fail safe mini-pressostat
Access door(s)
Acoustic insulation
Condensing unit electronic controller
Network connectivity
Stack mounting
Discharge gas thermostat
HP/LP Alarm
Liquid injection kit, phase loss/sequence protection
Pressure Relief Valve (Provision)**
* Inbuilt function within Condensing unit electronic controller
** PRV factory fitted in PED cat. II models
Compressor
Electrical
Refrigerant
Model
Code
VLZ028TGA
E
VLZ035TGA
E
VLZ044TGA
E
PS
Receiver
PED
(L)
category*
bar
P
6.2
I
32
P
6.2
I
32
P
6.2
I
32
118A5499A - AN1871864252420
(P01)
IP54
Scroll with Inverter
yes
yes
yes
yes
-
yes
yes
yes
Electronic
Mechanical
yes
yes
yes
yes
yes
yes
yes
-
Yes
Suction
Liquid
Unit Dimensions
Valve
Valve
Housing
Inch
Inch
L
3/4"
5/8"
H3
965
3/4"
5/8"
H3
965
3/4"
5/8"
H3
965
(mm)
W
H
1441
531
1441
531
1441
531
| 39
3-000601