7. Connection of building control technology
The TECE hygiene flush can be connected to the building control technology via
EN
a 5-pin potential-free contact. This interface is independent of the system and
can be combined with any BCT.
Both input signals can be used to control and switch on the warm and cold water
flush valves. The flush volume can be regulated/set via the opening time for the
valves (5 l/min).
Additionally, the two output signals offer the ability to transmit flushes performed
by the hygiene flush to the BCT and document these.
TECE
valve 1 OUT
valve 2 OUT
GND
valve 1 IN
valve 2 IN
male
5
4
BCT interfaces
Practical tip: If the TECE hygiene flush is controlled via BCT, the pre-installed
„ApplicationBCT" flush programme can be used to deactivate the flush pro-
grammes (as well as factory settings) on the electronics.
28
5
white
4
brown
1
red
3
green
2
yellow
1
2
3
BCT
valve off = high signal (12 V DC, 3 mA)
valve on = low signal (0 V DC)
potential-free NO contact