TInstallation of ceiling opening and
hanging bolt
Hanging bolt
Level vial
Hanging bracket
Attach a nut (M10 or W3/8: not supplied) and the
•
Ø34 washer (supplied) to each hanging bolt.
Insert a washer on both sides of the T groove of the
•
hanging bracket of the indoor unit, and hang the
indoor unit.
Check that the four sides of the indoor unit are level
•
using a level vial (levelness: 5 mm or less).
Detach the installation gauge (accessory) from the
•
installation pattern.
Using the installation gauge, check and adjust the
•
positional relation between the indoor unit and the
ceiling opening (1) (10 to 35 mm: 4 sides) and the
hanging-up height (2) (12
+5
mm: 4 corners).
0
(How to use the installation gauge is printed on the
gauge.)
* Procure hanging bolts
and nuts locally.
Hanging bolt
(M10 or W3/8)
Washer (Accessory)
Nut (M10 or W3/8)
To prevent the bolt
from falling off (for
safety), be sure to set
Eccentric washer
it just under the
(Accessory)
hanging bracket as
* Install with the marking
shown in the figure.
"UP" facing up.
Nut (M10 or W3/8)
109-EN
Level vial (levelness: 5 mm or less)
Hanging bolt
Indoor unit
Hanging
bracket
(1) 10 to 35 mm
Ceiling
board
nstallation gauge
Indoor unit
(2)
12
+5
Ceiling board
Installation
mm
0
(1) 10 to
gauge
35 mm
REQUIREMENT
Before installation of the indoor unit, be sure to remove
the tape for transportation between the fan and the bell
mouth. Running the unit without removing the tape may
damage the fan motor.
Be sure to remove the tape for
transportation between the fan and the
bell mouth.
– 55 –
Installation of ceiling panel
(Sold separately)
Install the ceiling panel according to Installation
Manual attached with it after piping / wiring work has
completed.
Check that installation of indoor unit and ceiling
opening part is correct, and then install it.
REQUIREMENT
Joint the connecting sections of ceiling panel, ceiling
•
surface, ceiling panel and indoor unit closely.
Any gap between them will cause air leakage and the
generate condensation or water leakage.
Remove the adjust corner caps at the four corners
•
of the ceiling panel, and then install the ceiling panel
onto the indoor unit.
Make sure that the claws of the four adjust corner
•
caps are securely fit.
* Improper fitting of the claws may cause water
leakage.
Installation of remote
controller (Sold separately)
For installation of the wired remote controller, follow
the Installation Manual attached with the remote
controller.
Pull out the remote controller cord together with the
•
refrigerant pipe or drain pipe.
Be sure to pass the remote controller cord through
upper side of the refrigerant pipe and drain pipe.
Do not leave the remote controller at a place exposed
•
to the direct sunlight and near a stove
In case of wireless type
The sensor of indoor unit with wireless remote
controller can receive a signal by distance within
approx. 8 m. Based upon it, determine a place where
the remote controller is operated and the installation
place.
Operate the remote controller, confirm that the indoor
•
unit receives a signal surely, and then install it.
Keep 1 m or more from the devices such as
•
television, stereo, etc.
(Disturbance of image or noise may generate.)
To prevent a malfunction, select a place where is not
•
influenced by a fluorescent light or direct sunlight.
Two or more (Up to 6 units) indoor units with wireless
•
type remote controller can be installed in the same
room.
Signal receiving unit
8 m
110-EN