7. Service
■ Mr. Slim output contents
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
1
2
3
4
5
6
en
7
8
9
10
11
12
14
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.) * The supported check codes may
vary depending on the connected outdoor unit.
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
[Output pattern C] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
9
14
Wired remote
controller
Check code
P1
Intake sensor error
P2, P9
Pipe (liquid or 2-phase pipe) sensor error
E6, E7
Indoor/outdoor unit communication error
P4
Drain sensor error/Float switch connector open
P5
Drain overflow protection operation
PA
Forced compressor error
Freezing (during cooling operation)/Overheating protection operation
P6
(during heating operation)
EE
Assembly error (system error)
P8
Pipe temperature error
E4
Communication error between wired remote controller and indoor unit
Pb
Indoor unit fan motor error
Fb
Indoor unit control system error (memory error, etc.)
PL
Refrigerant circuit abnormal
Wired remote
controller
Check code
E9
Indoor/outdoor unit communication error
UP
Compressor overcurrent interruption
U3, U4
Open/short of outdoor unit thermistors
UF
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/insufficient refriger-
U2
ant
U1, Ud
Abnormal high pressure (63H worked)/Overheating protection operation
U5
Abnormal temperature of heat sink
U8
Outdoor unit fan protection stop
U6
Compressor overcurrent interruption/Abnormal of power module
U7
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and abnormal
U9, UH
synchronous signal to main circuit/Current sensor error
Others
Other errors (Refer to the technical manual for the outdoor unit.)
Wired remote
controller
Check code
EH
Panel communication abnormal (auto ascending/descending panel)
Symptom
Symptom
Symptom
Remark
Remark
For details,
check the LED
display of the
outdoor con-
troller board.
Remark
Tabla de contenido
loading

Tabla de contenido