Use 75 °C copper wire only - models with suffix 0075, 0110, 0370, 0450, 0550,
0750, 0900, 1100, 1320, 1600, 2000, 2500.
Use 60/75 °C copper wire only - models with suffix 0005, 0008, 0011, 0014, 0015,
0022, 0030, 0037, 0040, 0055, 0150, 0220, 0300.
•
Tighten terminals to in-lbs (Nm) as follows:
Series
Size
®
MOVIDRIVE
0XS, 0S, 0L
MDX 60B/61B
1, 2S
2
3
4, 5
6
7
Field wiring is to be made using listed ZMVV Lugs - models size 2, 3, 5.
Suitable for use on a circuit capable of delivering not more than
•
200,000 rms symmetrical amperes when protected by fuses and circuit breakers
as described in the tables below.
•
65,000 rms symmetrical amperes when protected by ABB and Rockwell Type E
Combination Motor controllers as described in the tables below.
®
•
MOVIDRIVE
MDX60B/61B 0005 - 2500 (400 V units only).
Max. voltage is limited to 500 V.
®
•
MOVIDRIVE
MDX60B/61B 0015 - 0300 (230 V units only).
Max. voltage is limited to 240 V.
®
MDX60B/61B
in-lbs
Nm
5
0.6
5
0.6
13
1.5
31
3.5
120
14
180
20
620
70