SYSTEM SETTINGS
Blueface
•
System address (not available on systems with BACnet gateway). Defines the number of the system within your
installation. The Supermaster option (available in installations with Airzone production control board, AZX6CCP) allows
ES
you to impose the operation mode of the system to the rest of the systems connected to the AZX6CCP (in a semi-
forced way).
EN
FR
IT
PT
DE
•
Temperature range. Selects the highest temperature in heating mode (19-30 ˚C, 30˚C by default) and the lowest
temperature in cooling mode (18-26 ˚C, 18˚C by default). It is also possible to disable some of the modes.
•
Combined stage. (only available in installations with AZDI6OUTPUT8 modules) Enables activating and deactivating the
combined stage of the "Control Stages" parameter in the user's Zone Settings Menu.
•
Hysteresis Configuration. Defines the temperature differential between room temperature and set-point
temperature required to start applying the RadianT algorithm (if the control stage is set as radiant) or to apply the
Combined Algorithm (if the control stage is set as combined). In installations with radiators, set this value to 0ºC. It is
set to 0ºC by default.
•
Standby Mode. Allows motorized elements to be kept open in cooling/heating mode when the set-point temperature
has been reached and the AC unit remains switched on in low consumption mode. However, if it is deactivated, the
AC unit will turn off and the motorized elements will close.
•
Standby Hysteresis. (Only available when Standby mode is activated.) Allows you to set the activation temperature
for Standby mode (by default it is activated at 16 °C in heating mode and at 30 °C in cooling mode). The initial setting
for hysteresis is 0 °C.
•
Type of opening (only available in installations with AZDI6MZZON [C/R] modules). Use this parameter to configure the
type of opening of the damper output: All/Nothing (by default) or Proportional.
*Note: If you change this parameter, all the dampers of the installation will be affected. It is not recommended for RINT and
RIC intelligent grilles.
•
Minimum air (only available in installations with AZDI6MZZON [C/R] module and with the parameter Type of opening
configured as proportional). This allows the access of a minimum air flow in zones where the set-point temperature has
been already reached.
*Note: If you change this parameter, all the dampers of the installation will be affected. It is not recommended for RINT and
RIC intelligent grilles.
•
Relay settings. Use this parameter to change the operation logic of the CMV/Boiler of the system main control board.
•
Boiler temperature (only available in installations with AZX6CCP). Sets a cut-off temperature for the boiler in order to
protect it. Range: 40-65 ˚C (by default).
•
Return temperature (only available in installations with AZX6SONDPROTEC protection probes). Defines the cut-off
temperatures in heating mode (32˚C, 34˚C and 36˚C) and cooling mode (6˚C, 8˚C and 10 ˚C) to protect the AC unit. The
system highest temperature by default is 30˚C and the lowest is 18˚C.
•
Radio channel. It activates/deactivates the Wireless association module of the system.
38
Operation modes:
System 1
Available operation modes:
Rest