INITIAL CONFIGURATION EVALUATION

Check the following aspects:
-
AC unit-system communication: Choose any mode (except for STOP mode) and switch on the zone to generate
demand. Verify that the selected operation mode in the Master thermostat is shown in the indoor unit thermostat and
the set-point temperature changes.
-
Opening-closing of the dampers, ON/OFF of individual AC units and control outputs: Turn on the system and generate
demand in all the zones. Then, switch off and on each zone to verify the element to be controlled operates properly.
-
Verify that the static pressure of the duct system complies with the air distribution network conditions where is
installed (check the Manufacturer's Manual of the equipment if you need to modify this parameter).
Remember: For security reasons, the last zone takes 4 minutes to close.
Important: After the setup or in case of power outage, the system takes a few minutes to measure precisely the temperature
and the relative humidity.
Important: when the system stops generating demand, the motorized elements of the activated zones will remain open and
the unit will remain on, setting a set-point temperature of 30˚C for cooling mode and 16˚C for heating mode.

ADVANCED SETTINGS

To access the advanced configuration menu of the thermostat and Blueface Think follow the following steps:
Blueface
Press and hold
Think
Press once
From this menu you can control both the zone parameters and the system parameters.
Press and hold
Press and hold