BTL5-H1 _ _ -M _ _ _ _ -A/B/Y/Z(8)-S94
Magnetostrictive Linear Position Sensor – Rod Style
The CE Mark verifies that our products
meet the requirements of the current
EMC Directive.
Intended use
The magnetostrictive linear position sensor BTL, together
with a CANopen
master (e.g. PLC) comprises a position
®
measuring system. It is intended to be installed into a
machine or system and used in the industrial sector.
Flawless function in accordance with the specifications in
the technical data is ensured only when using original
Balluff accessories. Use of any other components will void
the warranty.
Opening the BTL or non-approved use are not permitted
and will result in the loss of warranty and liability claims
against the manufacturer.
General safety notes
Installation and startup may only be performed by
trained specialists.
The operator is responsible for ensuring that local safety
regulations are observed. In particular, the operator must
take steps to ensure that a defect in the BTL will not result
in hazards to persons or equipment.
If defects and unresolvable faults occur in the BTL, take it
out of service and secure against unauthorized use.
Downloading further instructions
A complete user's guide and the configuration guide can
be downloaded from the Internet at www.balluff.com or
Dimensions and function
The BTL contains the waveguide which is protected by an
outer stainless steel tube (rod). A magnet is moved along
the waveguide. This magnet is connected to the system
part whose position is to be determined. The magnet
defines the position to be measured on the waveguide.
Mounting surface
Version
D1
...-A/B/Y/Z-...
10,2 mm
...-A/B/Y/Z8-... 8 mm
1
english
B: 30 -1 mm
Z: 2" -0.04"
Nominal length =
Measuring range
2)
Magnet 1)
Mounting surface
Thread size:
B: M18x1.5
Z: 3/4"-16UNF
G
Thread
M4x4/6 deep
No thread
Electrical connection
Pin
BTL5-H1...-S94
1
CAN_GND (BUS IN / OUT)
2
3
4
CAN_H (BUS IN / OUT)
5
CAN_L (BUS IN / OUT)
Configuration
Node ID: adjustable via S1.1...S1.6;
Value 0 = LMT setting
S1.1
S1.2
S1.3
2
0
2
1
2
2
LSB
1
2
4
Baud rate [kBaud]: adjustable via S1.7...S1.9
S1.7
S1.8
S1.9
2
0
2
1
2
2
LSB
–
MSB
1
2
4
Set Value Baud rate
1
1000
2
800
3
500
4
250
Bus termination: Termination for S1.10 = ON
Damping zone 2)
A: 30 -1 mm
Y: 2" -0.04"
Thread size:
A: M18x1.5
1) Not included in scope of delivery
Y: 3/4"-16UNF
2) Unusable area
UL approval
File No.
E227256
+24 V
0 V (GND)
S1.4
S1.5
S1.6
2
3
2
4
2
5
MSB
8
16
32
Set Value
Baud rate
5
125
6
100
7
50
0
LMT setting