49 00
Automatic reclosing attempts after safety edge or the anti-crushing protection intervention
00
does not automatically reclose after the safety edge or the anti-crushing protection intervention
01
03
number of attempts at reclosing
-
If the value exceeds that of parameter
a2
parameter
50 00
Mode if photocell FT1 is interrupted when opening
00
IGNORE, no action or FT1 not installed
01
STOP, the gate remains stationary until the next command
02
REVERSE IMMEDIATELY, thus closing
03
TEMPORARILY STOP, the beam released, it continues to open
04
INVERT WHEN RELEASED, the beam released, it reverses thus closing
51 02
Mode if photocell FT1 is interrupted when closing
00
IGNORE, no action or FT1 not installed
01
STOP, the gate remains stationary until the next command
02
REVERSE IMMEDIATELY, thus closing
03
TEMPORARILY STOP, the beam released, it continues to open
04
INVERT WHEN RELEASED, the beam released, it reverses thus closing
52 00
With the gate closed permits opening with FT1 obscured
00
does not permit opening
01
permits opening
02
OPENS WHEN IT IS OBSCURED
53 03
Mode if photocell FT2 is interrupted when opening
00
IGNORE, no action or FT2 not installed
01
STOP, the gate remains stationary until the next command
02
REVERSE IMMEDIATELY, thus closing
03
TEMPORARILY STOP, the beam released, it continues to open
04
INVERT WHEN RELEASED, the beam released, it reverses thus closing
54 02
Mode if photocell FT2 is interrupted when closing
00
IGNORE, no action or FT2 not installed
01
STOP, the gate remains stationary until the next command
02
REVERSE IMMEDIATELY, thus closing
03
TEMPORARILY STOP, the beam released, it continues to open
04
INVERT WHEN RELEASED, the beam released, it reverses thus closing
55 00
With the gate closed it permits opening with FT2 obscured
00
does not permit opening
01
permits opening
02
OPENS WHEN IT IS OBSCURED
. Only recloses after the impact if it is moved back until fully open.
a2
, it will be automatically considered to be equal to that of
33