Refrigerant Piping Work; Refrigerant Pipe; Pipe Connection; Flaring Work - Mitsubishi Electric Mr.SLIM SEZ-KC25VA Manual De Instalación

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 37
6. Installing the unit
Caution:
Be sure to install the unit body at level.

7. Refrigerant piping work

7.1. Refrigerant pipe

[Fig. 7-1] (P.3)
a Indoor unit
b Outdoor unit
[Fig. 7-2] (P.3)
a Indoor unit
b Outdoor unit
Maximum difference between heights of indoor unit and outdoor unit, the length of
refrigerant piping and the number of bends in piping are within limits shown below.
Models
(A) Pipe length
(one way)
SEZ-KC25VA
max. 20 m
*1: Height difference limitations are binding regardless of which unit, indoor or out-
door, is positioned higher.
Avoid the following places for installation where air conditioner trouble is liable to
occur.
• Where there is too much oil such as for machine or cooking.
• Salty environment as seaside areas.
• Hot-spring areas.
• Where sulfide gas exists.
• Other special atmospheric areas.
• This unit has flared connections on both indoor and outdoor sides. (Fig. 7-2)
• Refrigerant pipes are used to connect the indoor and outdoor units as shown in the
figure below.
• Insulate both refrigerant and drainage piping completely to prevent condensation.
• Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant (R410A)
charge is required.
(The outdoor unit is charged with refrigerant for 7 m pipe length.)
7 m
No additional
maximum
charge required
Exceeding
Additional
7 m
charge required
Piping preparation
• Refrigerant pipes of 3, 5, 7, 10 and 15 m are available as optional items.
(1) Table below shows the specifications of pipes commercially available.
Outside diameter
Model
Pipe
mm
inch
For liquid
6.35
1/4
SEZ-
KC25VA
For gas
9.52
3/8
(2) Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
(3) Refrigerant pipe bending radius must be 10 cm or more.
Caution:
Using careful insulation of specified thickness. Excessive thickness prevents
storage behind the indoor unit and smaller thickness causes dew drippage.

7.2. Flaring work

• Main cause of gas leakage is defect in flaring work.
Carry out correct flaring work in the following procedure.
7.2.1. Pipe cutting
[Fig. 7-3] (P.3)
a Copper tubes
b Good
c No good
d Tilted
e Uneven
f Burred
• Using a pipe cutter cut the copper tube correctly.
(B) Height
(C) Number of
difference
bends (one way)
max. 12 m
max. of 10
Refrigerant
30g/m
to be added
Min wall
Insulation
Insulation
thickness
thickness
material
Heat resisting
0.8 mm
8 mm
foam plastic
0.045 specific
0.8 mm
8 mm
gravity
7.2.2. Burrs removal
[Fig. 7-4] (P.3)
a Burr
b Copper tube/pipe
c Spare reamer
d Pipe cutter
• Completely remove all burrs from the cut cross section of pipe/tube.
• Put the end of the copper tube/pipe to downward direction as you remove burrs in
order to avoid burrs drop in the tubing.
7.2.3. Putting nut on
[Fig. 7-5] (P.3)
a Flare nut
b Copper tube
• Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube
having completed burr removal.
(not possible to put them on after flaring work)
7.2.4. Flaring work
[Fig. 7-6] (P.3)
a Flaring tool
b Die
c Copper tube
d Flare nut
e Yoke
• Carry out flaring work using flaring tool as shown below.
Pipe diameter
A (mm)
(mm)
When the tool for R410A is used
Clutch type
6.35
0 - 0.5
9.52
0 - 0.5
12.7
0 - 0.5
15.88
0 - 0.5
Firmly hold copper tube in a die in the dimension shown in the table at above.
7.2.5. Check
[Fig. 7-7] (P.3)
a Smooth all around
b Inside is shining without any scratches
c Even length all around
d Too much
e Tilted
• Compare the flared work with a figure in right side hand.
• If flare is noted to be defective, cut off the flared section and do flaring work again.

7.3. Pipe connection

[Fig. 7-8] (P.3)
• Apply a thin coat of refrigeration oil on the seat surface of pipe.
• For connection first align the center, then tighten the first 3 to 4 turns of flare nut.
• Use tightening torque table below as a guideline for indoor unit side union joint section,
and tighten using two wrenches. Excessive tightening damages the flare section.
Copper pipe O.D.
Flare nut O.D.
(mm)
ø6.35
ø9.52
ø12.7
ø15.88
Warning:
Be careful of flying flare nut! (Internally pressurized)
Remove the flare nut as follows:
1. Loosen the nut until you hear a hissing noise.
2. Do not remove the nut until the gas has been completely released (i.e., hiss-
ing noise stops).
3. Check that the gas has been completely released, and then remove the nut.
Outdoor unit connection
Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied
for indoor unit.
• For tightening use a torque wrench or spanner, and use the same tightening torque
applied for indoor unit.
Dimension
+0
B
(mm)
-0.4
9.1
13.2
16.6
19.7
f Scratch on flared plane
g Cracked
h Uneven
i Bad examples
Tightening torque
(mm)
(N·m)
17
14 - 18
22
34 - 42
26
49 - 61
29
68 - 82
9
Tabla de contenido
loading

Tabla de contenido