11.3.3 Error type C
1
2
3
4
5
6
7
8
Fig. 49: Error type C, flowchart
6.0.0.0
E000
6.0.0.0
- - -
3/6
6.0.0.0
300
5/6
6.0.0.0
6/6
Fig. 50: Acknowledging error type C
Installation and operating instructions LRE, JRE
E000
12.3
S
E000
12.3
S
0
12.3
S
Error type C (Fig. 49):
Program
Contents
step/query
1
• Error code is displayed
• Motor Off
• Red LED On
2
Error criterion fulfilled?
3
> 5 minutes?
4
• Error counter is incremented
5
Error counter > 5?
6
• SSM is activated
7
Error acknowledged?
8
End; auto control resumes
Yes
No
If type C errors occur, proceed as follows to acknowledge (Fig. 50):
• To change to the menu mode, press the white button.
Menu number <6.0.0.0> flashes on the display.
• Press the white button again.
Menu number <6.0.0.0> appears steady on the display.
On the value display, "- - -" appears.
On the units display, the current incidence (x) as well as the maximum
incidence of the error (y) are displayed in the format "x/y".
After 300 seconds, the current incidence will be counted up by one.
NOTE:
The error will be acknowledged automatically if the cause of the error
is eliminated.
• Wait until the remaining time is up.
If the current incidence (x) is the same as the maximum incidence of
the error (y), this error can be acknowledged manually.
• Press the white button again.
The error is acknowledged, and the status page is displayed.
English
109