Table 5: P0275...P0279 options for indication of state of inverter or faults on DOx digital outputs
DOx Digital Output Function
State of the inverter = STO
(safety stop function activated).
F160 fault
(inverter tripped by safety stop
function fault actuation).
Fault (inverter tripped by
actuation of any fault).
Without fault
(state of the inverter is not fault).
Refer to CFW-11 inverter programming manual for a complete list of options for parameters
P0275...P0279.
3.4 PERIODIC TEST
Safety stop function, alternatively safety stop inputs (STO1 and STO2), must be activated at
least once a year for preventive maintenance purposes. Inverter power supply must be switched
off and then on again before carrying out this preventive maintenance. If during testing the
power supply to the motor is not switched off, safety integrity is no longer assured for the
safety stop function. The drive must therefore be replaced to ensure the operational safety of
the machine or of the system process.
4 EXAMPLES OF WIRING DIAGRAMS OF INVERTER CONTROL SIGNAL
It's recommended to use inverter DI1 and DI2 digital inputs set as 3-wire start/stop commands
and the wiring diagrams of inverter control signal according to figure 4.
Value to Be Set
on P0275...P0279
CFW-11 and
CFW70x
CFW-11M
33
30
34
31
13
13
26
24
Safety Stop Function
Comment
Safety stop function disabled:
relay/transistor OFF.
Safety stop function activated:
relay/transistor ON.
Without F160 fault: relay/transistor OFF.
With fault F160: relay/transistor ON.
Without fault: relay/transistor OFF.
With fault: relay/transistor ON.
With fault: relay/transistor OFF.
Without fault: relay/transistor ON.