Plc11 - 02 Hardware Features; Configurations - WEG CFW-11 Guía De Instalación, Configuración Y Operación

Ocultar thumbs Ver también para CFW-11:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

2. PLC11 - 02 HARDWARE FEATURES

The PLC11 - 02 accessory has the following hardware features:
- 4 isolated and bi-directional digital inputs, two of them are fast and may generate
interrupts.
- 1 relay digital output 250 V @ 3 A;
- 3 opto-isolated and bi-directional digital outputs 24 V @ 500 mA;
- 2 isolated encoder inputs, with internal power supply (5 VDC or 12 VDC);
- 1 RS-485 serial communication interface (Standard protocol: MODBUS-RTU);
- 1 CAN interface.

3. CONFIGURATIONS

Table 1: Configuration of the PLC11 - 02 switches
Switches
Function
Failure detection on
S4:1
encoder signals A, A , B, B ,
Z, Z (F079)
Voltage from the regulated
S4:2
power supply that feeds the
encoder
S5:1
RS-485 interface
S5:2
termination resistor
(*) Factory standard.
Position
ON
Failure detection disabled
OFF
Failure detection enable
(*)
ON
5 VDC
OFF
12 VDC
(*)
ON
Enables the termination resistor
Disables the termination
OFF
(*)
resistor
Figure 4: Location of the configuration switches
Setting
Set according to the voltage
of the encoder used
This resistor must be
enabled (with both switches
S5:1 and S5:2 in the ON
position) only at the two
devices located at the main
bus extremes
Observations
-
S4
S5
3
Tabla de contenido
loading

Este manual también es adecuado para:

Plc11- 02

Tabla de contenido