Adjustment - SICK IN4000 Standard Manual Del Operador

Ocultar thumbs Ver también para IN4000 Standard:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Operating Instructions
IN4000 Standard
Note
© SICK AG • Industrial Safety Systems • Germany • Subject to change without notice 8010934/WQ88/2013-01-15
Connection and adjustment
The following applies to cuboid sensors:
Cable diameter control
circuit
AWG
(mm²)
26
(0.13)
24
(0.20)
22
(0.32)
20
(0.52)
18
(0.82)
16
(1.3)
5.2

Adjustment

To determine a suitable mounting position, the sensor
can be placed in an adjustment mode.
Hold metal object in the near range (cf. Fig. 1 and,
depending on the sensor type, tab. 1, 2 or 3) of the
sensor for around 5 s; the sensor is in the
adjustment mode when the yellow signal LED
flashes
The output remains in the safe state in the adjustment
mode.
To identify the enable zone, move the actuating
element in front of the sensor; the yellow signal LED
extinguishes when the actuating element is in the
enable zone
Mount sensor and actuating element in the position
found
Switch off adjustment mode by interrupting the
power supply or removing the activation for more
than 2 s
Overcurrent protection
Maximum load of the protective
Chapter
device
Ampere
1
2
3
5
7
10
177
5
Tabla de contenido
loading

Tabla de contenido