Dometic Waeco SinePower MSI2312T Instrucciones De Montaje página 47

Ocultar thumbs Ver también para Waeco SinePower MSI2312T:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 81
SinePower
➤ Set the main switch (fig. 5 3, page 4) to "OFF" and make sure that the
connection for the remote control (fig. 5 12, page 4) is not assigned.
➤ Set the main switch (fig. 5 3, page 4) to "REMOTE".
➤ Connect the external on/off switch with the connection cable to the green
terminal (fig. 5 11, page 4).
9.9
Connecting parallel operation
A
NOTICE!
 Use a cable with a cross section of 0.25 – 0.75 mm² for con-
necting to the terminals for parallel operation.
 Parallel operation can only be set up using the same models
(same item number).
 A maximum of three inverters can be operated in parallel.
 The inverters operating in parallel must have the same set-
tings for mains voltage and mains frequency. (see chapter
"Configuring the inverter" on page 50.
➤ Set the main switch (fig. 5 3, page 4) to "OFF".
➤ Connect the inverter according to the sample circuit diagram (fig. b,
page 7).
In particular, make sure that the bridges for parallel operation are set
correctly:
 Bridge removed (fig. b 1, page 7) for inverter A and set for inverter B and
C.
I
NOTE
The first inverter which is switched on after installing parallel
operation is the master.
EN
Connecting the inverter
47
Tabla de contenido
loading

Tabla de contenido