Control Functions; Alarm Messages - Schneider Airsystems Air Master Serie Manual De Instrucciones

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 51
PARAMETERS
Oil temp. pre-alarm (delta)
Maximum oil temperature
Minimum oil temperature
Empty time
Maintenance pre-alarm
Fan temperature
Automatic start
Pressure sensor
PSI/BAR

ALARM MESSAGES

In the case of anomalies or if the set safety limits are exceeded, the red alarm light switches on and the alarm in progress is
visualised on the display.
1) Control of the direction of rotation
It is activated in the case of incorrect phase sequence. The alarm blocks the compressor. To
re-activate functioning the phases must be first restored.
N.B To reset the alarm completely the electric power supply must be removed
2) Control temperature probe
It is activated if the temperature probe breaks (probe open or in short circuit). The alarm
blocks the compressor. To restore functioning check the connection and/or replace the probe
.
and press the key
3) Maximum oil temperature
It is activated when the maximum oil temperature is reached. The alarm blocks the compressor.
To re-start wait for the temperature to fall below the programmed value and act on the button
4) Minimum oil temperature
It is activated when the minimum oil temperature is reached. The alarm blocks the compressor.
To re-start wait for the temperature to rise above the programmed value and act on the button
5) Oil temperature pre-alarm
It is activated when the oil pre-alarm value has been reached. The alarm does not block the
compressor. Act on the button
6) Motor circuit breaker
It is activated when the motor circuit breaker relay intervenes. The alarm blocks the compressor.
Act on the button
to silence the alarm after the cause has been verified.
7) Emergency
It is activated when the emergency button is pressed which blocks the compressor. Act on the
button
to silence the alarm after having restored the status of the emergency button.
8) Machine maintenance pre-alarm
This alarm informs the user that the machine requires routine maintenance (oil change, filters,
etc.). The alarm must be silenced by the operator that carries out the maintenance by selecting
"Pre-alarm times" from the menu and by restoring the value as described in the "Parameters that
can be modified" – chapter point (1).
9) Pressure separator switch
It is activated on opening of the pressure separator gauge contact. The alarm blocks the
compressor. To silence the alarm press the
pressure separator gauge.
10) Fault 4-20 mA (pressure sensor)
It is activated when the pressure sensor connected to the 4-20mA input does not function
correctly. The alarm blocks the compressor. To silence the alarm press the
having restored the normal status of the pressure sensor
11) Maximum pressure
It is activated when the maximum set pressure is exceeded. The alarm blocks the compressor. To
silence the alarm press the
12) Inverter faulty
Press the key
to silence the alarm. If problem persists, contact a service center without
delay.

CONTROL FUNCTIONS

Min.
Max.
Standard
°C
0
20
°C
0
150
-14
0
°C
1
250
sec.
Hours
0
32768
4000
°C
0
150
YES
NO
YES
NO
PSI
BAR
bar
to silence the alarm
key after having restored the normal status of the
key after having restored the correct pressure
5
Set empty/press.functioning
110
Delta functioning
-7
Max pressure that can be set
75
Max pressure alarm
Load dela
80
Internal phase sequence
NO
Language
YES
Display contrast level
BAR
Enabling of RS485
key after
.
bar
0
15
8/10/13
bar
0
2
1
bar
0
15
9/11/14
bar
0
16
14
sec.
0
200
10
YES
NO
YES
ITA
1
20
5
YES
NO
YES
30°C h00110 m05
Incorrect dir.of rot.
30°C h00110 m05
Temp. sens. fault
110°C h00110 m05
Max. oil temp.
-10°C h00110 m05
Min. oil temp.
105°C h00110 m05
Oil temp. pre-alarm
74°C h00110 m05
Motor circuit breaker
74°C h00110 m05
Emergency button
74°C h00110 m05
Routine maintenance
74°C h00110 m05
Press.Separate. switch
74°C h00110 m05
4-20Ma fault
74°C h00110 m05
Max. pressure
74°C h00110 m05
Inverter faulty
GB
11
11
11
11
11
Tabla de contenido
loading

Tabla de contenido